Table 5.12 Protection
Phase Overcurrent
51P-1 PH TOC
51P-2 PH TOC
50P-1 PH IOC 1
50P-1 PH IOC 2
IX Overcurrent
51X IX TOC
50X-1 IX OC 1
50X-1 IX OC 2
IR Overcurrent
51R IR TOC
50R-1 IR IOC 1
50R-1 IR IOC 2
47-1 V Unbal
46-1 Current Unbal
Effective Date: 12/05
FP-5000
PH Settings
Shape:
Reset:
Direction:
Pickup:
Time Mult:
Shape:
Reset:
Direction:
Pickup:
Time Mult:
Vrestraint:
Pickup:
Delay (c):
Direction:
Pickup:
Delay (c):
Direction:
IX Settings
Shape:
Reset:
Direction:
Pickup:
Time Mult:
Pickup:
Delay (c):
Direction:
Pickup:
Delay (c):
Direction:
IR Settings
Shape:
Reset:
Direction:
Pickup:
Time Mult:
Pickup:
Delay (c):
Direction:
Pickup:
Delay (c):
Direction:
47-1 Voltage Unbalance Alarm Settings
Threshold:
% (I2/I1):
Delay (c):
46-1 Current Unbalance Alarm Settings
Threshold:
% (V2/V1):
Delay (c):
For more information visit:
Effective Date: 12/05
www.eatonelectrical.com
IL17569C
Page 5-57
Default Setting
MOD
Calc
Both
1.00
1.00
MOD
Calc
Both
1.00
2.00
Disable
2.00
0
Both
3.00
15
Both
Default Setting
XTRM
Calc
Both
0.50
1.00
1.00
60
Both
2.00
6.00
Both
Default Setting
XTRM
Calc
Both
0.5
1.00
1.00
60
Both
2.00
600
Both
Default Setting
Disable
20
600
Default Setting
Disable
20
600
Page 5-57