Table 12.5 Event Pickup or Dropout Cause Table — continued
Cause
Cause Description
59N OV
Neutral Overvoltage has picked up or
dropped out
32 Power
Power Protections have picked up or
dropped out
27A UV
Auxiliary Undervoltage has picked
up or dropped out
46 Iunbal
Phase Current Unbalance has picked
up or dropped out
47 Vunbal
Phase Voltage Unbalance has picked
up or dropped out
81 UF
Underfrequency has picked
up or dropped out
81 OF
Overfrequency has picked
up or dropped out
BF
Breaker Failure has picked
up or dropped out
55A PF
Apparent Power Factor has picked
up or dropped out
55D PF
Displacement Power Factor has
picked up or dropped out
Zin Trip
Zone Interlock Trip has picked
up or dropped out
PwrAlm
The system alarm for Watt, VA, or
VAR has picked up or dropped out
PwrDmdAlm
The system alarm for Watt demand,
VA demand, or VAR demand has picked
up or dropped out
CurDmdAlm
The system alarm for Current Demand
has picked up or dropped out
THD CurAlm
The system alarm for Current Total
Harmonic Distortion has picked up
or dropped out
THD VolAlm
The system alarm for Voltage Total
Harmonic Distortion has picked up
or dropped out
LOP
Loss of potential has pickup or dropped
off
Coldload
Coldload pickup has been on or off
Page 12-6
FP-5000
For more information visit:
Value Given
Voltage Pickup Status - contains the status flags that
describe all under and overvoltage pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Voltage Pickup Status – contains the status flags that
describe all under and overvoltage pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
Miscellaneous Pickup Status – contains the status flags
that describe all unbalance, frequency, breaker failure,
power factor, power and zone interlocking pickups
System Alarm Pickup Status – contains the status flags for
all system alarms
System Alarm Pickup Status – contains the status flags for
all system alarm pickups
System Alarm Pickup Status – contains the status flags for
all system alarm pickups
System Alarm Pickup Status – contains the status flags for
all system alarm pickups
System Alarm Pickup Status – contains the status flags for
all system alarm pickups
Voltage Pickup Status – contains the status flags that
describe all under and overvoltage pickups
Sync Control Status - contains the status flags for sync-
check and cold load conditions.