Eaton Cutler-Hammer FP 5000 Instruction Leaflet page 60

Protective relay
Hide thumbs Also See for Cutler-Hammer FP 5000:
Table of Contents

Advertisement

Table 5.2 Protection
Setting Group ______
Phase Overcurrent : Phase time overcurrent (51P-1 & 51P-2) and instantaneous (50P-1 & 50P-2) protective device
settings
Display Setting
Description
Phase Time Overcurrent Curve
51P-1 PH TOC
Element #1 Settings
Curve
Shape:
Select curve characteristic shape
Reset:
Select curve reset characteristics
Direction:
Select direction
51P-1 PH TOC
Phase Time Overcurrent Pickup and
Time Multiplier Element #1 Settings
Setting
Pickup:
Select current pickup value in per
unit values (x I
Time Mult:
Select Time Multiplier
Vrestraint
Reserved for later use
51P-2 PH TOC
Phase Time Overcurrent Curve
Element #2 Settings
Curve
Shape:
Select curve characteristic shape
Reset:
Select curve reset characteristics
Direction:
Select direction
51P-2 PH TOC
Phase Time Overcurrent Pickup and
Time Multiplier Element #2 Settings
Setting Pickup
Pickup:
Select current pickup value in per
unit values (x I
Time Mult:
Select Time Multiplier
Vrestraint
Select the maximum secondary
voltgage restraint level
Phase Overcurrent Element #1
50P-1 PH IOC 1
Setting
Pickup:
Select current pickup value in per
unit values (x I
Delay (c):
Select delay time in cycles
Direction:
Select direction
Effective Date: 12/05
FP-5000
Setpoint Range/
Value Selection
IT, I2T, I4T, FLAT, MOD,
VERY, XTRM, IECA, IECB,
IECC
Inst, Calc, T Delay
Forward, Reverse, Both
0.1 to 4.0
)
(0.01 increments)
nom
0.05 to 10.0
(.01 increments)
60 to 150 Volts or Disable
(Increments of 1)
(151=disable)
IT, I2T, I4T, FLAT, MOD,
VERY, XTRM, IECA, IECB,
IECC
Inst, Calc, T Delay
Forward, Reverse, Both
0.1 to 4.0
)
(0.01 increments)
nom
0.05 to 10.0
(.01 increments)
60 to 150 Volts or Disable
(Increments of 1)
(151=disable)
0.1 to 20.0
)
(0.01 increments)
nom
0 to 9999 cycles
(1 cycle increments)
Forward, Reverse, Both
For more information visit:
Effective Date: 12/05
or Disable
pu
or Disable
pu
or Disable
pu
www.eatonelectrical.com
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.2.1
8.3
MOD
13.4
Calc
Both
5.5.2.1
8.3
1.00
1.00
Disable
5.5.2.1
8.3
MOD
13.4
Calc
Both
5.5.2.1
8.3
1.00
2.00
Disable
5.5.2.1
8.3
2.00
0
Both
Page 5-5
IL17569C
Page 5-5

Advertisement

Table of Contents
loading