12.4.5 Upgrading Firmware

Upgrading Phase 1 firmware (version 1.0 or 1.03) to Phase 2 (or
later) will not be possible directly. A two-step process must be
completed.
First, download the boot swap code. To do this you must locate the
proper file. The default application file name (Fp5Kapp.s19) will
appear in the location window (see figure 12-5), this is not the file to
download at this time. To download the boot swap code to upgrade
type Fpbtswap.s19 in the file name box and click Open and follow
the normal upgrading procedures; this should take about one
minute. When the process completes, the relay will be in FlashLoad
mode and will prompt you to get the Phase 2 (or later) firmware, this
is the second step. Follow the normal procedures shown in this
section (see figures 12-8 through 12-15) to load the relay with the
newer application code.