IL17569C
Page 5-36
Effective Date: 12/05
Table 5.9 Cold Load Pickup:
Cold Load Pickup:
Display Setting
Description
Cold Load Pickup Cold Load Pickup Settings
Load Off Time:
Select the outage time required for
a load to be considered cold
Set Grp Enable:
Select the protection setting group
that the cold load pickup will be
applied to
Max Block Time:
Select the maximum amount of time
allowed for cold load pickup to be
active
Threshold:
Set the load current inrush
threshold
Settle Time
Select the amount of time for the
cold load inrush
Desensitize Gound Time
Desensitize Gnd
TOC
Overcurrent Settings
51X Pickup:
Select CT time overcurrent pickup in
a cold load condition
51R Pickup:
Select residual time overcurrent
pickup in a ocld load condition
Desensitize Phase Time
Desensitize Ph
TOC
Overcurrent Settings
51P1 Pickup:
Select phase time overcurrent 1
pickup in a cold load condition
51P2 Pickup:
Select phase time overcurrent 2
pickup in a cold load condition
Block Ix IOC
Block Fourth CT Overcurrent
Settings
50X-1
Select to block the CT overcurrent 1
while in cold load condition
50X-2
Select to block the CT overcurrent 2
while in cold load condition
50X-3
Select to block the CT overcurrent 3
while in cold load condition
Page 5-36
FP-5000
Setpoint Range/
Value Selection
0 to 120 minutes
(121 = disable)
(Increments of 1)
1, 2, 3, 4 or All
0 to 65535 seconds
(Increments of 1)
0.1 to 4
(Increments of 0.01)
0 to 65535 cycles
(Increments of 1)
0.1 to 4
(Increments of 0.01)
0.1 to 4
(Increments of 0.01)
0.1 to 4
(Increments of 0.01)
0.1 to 4
(Increments of 0.01)
Yes, No
Yes, No
Yes, No
For more information visit:
Default
Setting
Disable
1
600
51
pu
60
1
pu
1
pu
2
pu
2
pu
Yes
Yes
Yes
www.eatonelectrical.com
Selected
Refer to
Value
Sec. #
5.5.8
5.5.8
5.5.8
5.5.8
Effective Date: 12/05