Eaton Cutler-Hammer FP 5000 Instruction Leaflet page 74

Protective relay
Hide thumbs Also See for Cutler-Hammer FP 5000:
Table of Contents

Advertisement

Logging Settings (continued)
Display Setting
Description
Datalogger
Datalogger Settings
Mode:
Select mode of datalogger to be
continuous (overwrites) or 1-pass
Trigger:
Select trigger type
Interval (s):
Select interval of datalogging
in seconds
Value 1:
Set Value 1 to be logged
Value 2:
Set Value 2 to be logged
Value 3:
Set Value 3 to be logged
Value 4:
Set Value 4 to be logged
Value 5:
Set Value 5 to be logged
Value 6:
Set Value 6 to be logged
Value 7:
Set Value 7 to be logged
Value 8:
Set Value 8 to be logged
Waveform
Waveform Capture Settings
Capture
Records:
Select size of the waveform
capture using buffer x cycles
PreTrigger:
Select # of cycles of
preTrigger data
OSC Trigger
Select how to trigger waveform
TRIP2:
capture on Trip 2 operation
OSC Trigger
Select how to trigger waveform
dV/dI:
capture on a V or I disturbance
OSC Trigger
Select how to trigger waveform
Logic LG6:
capture on a LG6 logic operation
OSC Trigger
Select how to trigger waveform
Cntrl PB:
capture on pushbutton operation
OSC Trigger
Select how to trigger waveform
Comm:
capture on communication
command
Effective Date: 12/05
FP-5000
Setpoint Range/
Value Selection
Cont. or 1-Pass
Auto or manual
1 to 3600 seconds
(increments of 1)
IA, IB, IC, IX, IR, Iavg, I0,
I1, I2, VA, VB, VC, VX,
VLNavg, VAB, VBC, VCA,
VLLavg, V0, V1, V2, Freq,
W, VAR, VA, Dsp PF, App PF,
IA Demand, IB Demand,
IC Demand, W Demand,
VAR Demand, VA Demand,
Cin1, Cin2, Cin3, Cin4,
Cin5, Cin6, Cin7, Cin8,
LG1, LG2, LG3, LG4,
LG5, LG6, TG1, TG2,
TG3, TG4, TG5, TG6, IA
THD, IB THD, IC THD,
VA THD, VB THD, VC THD,
VAB THD, VBC THD,
VCA THD
4x64, 8x32, 16x16
(buffer x cycles)
1 to 15 cycles
(increments of 1)
Disable, Overwrite, or Lock
Disable, Overwrite, or Lock
Disable, Overwrite, or Lock
Disable, Overwrite, or Lock
Disable, Overwrite, or Lock
For more information visit:
Effective Date: 12/05
www.eatonelectrical.com
IL17569C
Page 5-19
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.4
8.11
Cont.
Auto
900
Ia
Ib
Ic
Ix
Va
Vb
Vc
Vx
5.5.4
8.10
16x16
2
Overwrite
Disable
Overwrite
Overwrite
Overwrite
Page 5-19

Advertisement

Table of Contents
loading

Table of Contents