IL17569C
Page 5-4
Effective Date: 12/05
Table 5.1 System Config (continued)
Display Setting
Description
Prg w/Bkr:
Program relay with breaker open or
closed (requires 52a or 52b input)
Remote Bkr:
Enable or disable remote breaker
open/close control from rear comm
port
# Set Grps:
Select the max. number of different
Protection Setting Groups
Set Ctrl:
Select the means of control for
selecting the active setting group
Disarm Ctrl:
Enable/disable of the Arm/Disarm
control from the front panel "Test
Mode' (Output Trip1 & Trip2 ONLY
Energy Unit:
This is the selection for "Energy
Units" killo- or Mega- watthours
TOC Reset T:
Time Overcurrent RESET Time
Delay in cycles. Used when time
option for reset is chosen
Bkr Oper PB:
Front panel Breaker Open/Close
pushbutton function Enable
Line Pos Seq
Select the positive sequence line
Impedance Ang:
impedance angle
Line Zero Seq
Select the zero sequence line
Impendance Ang:
impedance angle
IR Dir Cntrl:
Select the residual ground
polarizing method
Gnd Dir V 3V0
Select the zero sequence voltage
Source:
source for ground direction
polarizing
Gnd Dir V 310
Select the zero sequence voltage
Source:
source for ground direction
polarizing
IX Dir Cntrl:
Select I
Ph Dir Switch to
Select the memory voltage
Mem:
threshold
1
This setting affects other settings. The user must save settings after changing this setting, which will take the user
out of program mode. The user must then reenter program mode to continue programming the remaining settings.
2
If enabled, the user must go to the "Test Mode" by pressing the "test button", select Arm/Disarm Trip, then select Arm
Trip or Disarm Trip setting.
3
CT secondary rating is automatically detected: I
4
This setting is the programmed time delay for the T Delay setting of the time overcurrent
Curve settings for 51P, 51R, and 51X elements.
Page 5-4
ground polarizing method
x
For more information visit:
FP-5000
Setpoint Range/
Value Selection
Open or Either
Enable or disable
1
1, 2, 3 or 4
Local, Local+
Communications,
Communications, Cin
2
Enable or disable
kWh or MWh
4
1 to 20 cycles
Enable or disable
0 to 90 degrees
0 to 90 degrees
Off, dual, 3V0, I
, Neg
pol
Calculated, Measured
(0=Calculated, 1=Measured)
Calculated, Measured
(0=Calculated (Ir),
1=Measured(Ix))
Off, dual, 3V0, I
pol
1 to 15 Volts
(Increments of 1)
= 1 A or 5 A.
nom
www.eatonelectrical.com
Default
Selected
Refer to
Setting
Value
Sec. #
Either
5.5.1
Disable
5.5.1
1
5.5.1
9.7
Local
5.5.1
9.7
Disable
5.5.1
11.2.5.1
kWh
5.5.1
4.6.1.3
5
5.5.1
5.5.2.1
8.3.2
Disable
5.5.1
70
5.5.1
70
5.5.1
Off
5.5.1
Calculated
5.5.1
Calculated
5.5.1
Off
5.5.1
3
5.5.1
Reset setting. See TOC