Table 5.6 Output Configuration Settings
Output Configuration Settings: Phase time overcurrent (51P) and instantanious (50P-1 & 50P-2) device settings
Display Setting
Description
Output Trip 1 Relay Settings
Output Trip1
Monitor:
Select "Breaker Trip" coil circuit
monitoring to on or off
Function:
Select logic output function for
Output Trip1
Dropout:
Select relay state after trip occurs
Off Delay (c):
select delay for Trip Relay to
dropout after trip event clears
IN1:
Select logic input IN1 for Output
Trip1
IN2:
Select logic input IN2 for Output
Trip1
IN3:
Select logic input IN3 for Output
Trip1
IN4:
Select logic input IN4 for Output
Trip1
Output Trip2
Output Trip2 Relay Settings
Monitor:
Select "Close" coil circuit monitoring
to on or off
Function:
Select logic output function for
Output Trip2
Dropout:
Select relay state after trip occurs
Off Delay (c):
select delay for Trip2 Relay to
dropout after trip event clears
IN1:
Select logic input IN1 for Output
Trip2
IN2:
Select logic input IN2 for Output
Trip2
IN3:
Select logic input IN3 for Output
Trip2
IN4:
Select logic input IN4 for Output
Trip2
1 This setting is only used if the "Dropout" setting is set to "Off Delay."
Note: The I/O Configuration Setting in the System Configuration settings menu must be set to "custom" for these
set points to be configured. Otherwise the default settings displayed are used. See sections 5.4.5 and 5.4.6 for
details.
Effective Date: 12/05
FP-5000
Setpoint Range/
Value Selection
Off, On
OR, AND, NOR, NAND,
disable
Latched, unlatched, off delay Off Delay
0 to 600 cycles
1
(1 cycle increments)
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
Off, On
OR, AND, NOR, NAND,
disable
Latched, unlatched, off delay Unlatched
0 to 600 cycles
1
(1 cycle increments)
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
*See Logic Input Options
Table 5.10
For more information visit:
Effective Date: 12/05
www.eatonelectrical.com
Default
Selected
Refer to
Setting
Value
Sec. #
5.5.6
9.2
ON
9.6
OR
5
Trip AllProt
Cntrl,
OpenBkr
Unused
Unused
5.5.6
9.2
Off
9.6
Disable
0
Unused
Unused
Unused
Unused