event occurs. After pickup, if the watts fall
below the specified threshold, a power
dropout event occurs.
Delay (m):
Sets the number of minutes that the watts
must remain at or above threshold, before the
specified trip output occurs.
VAR Power Alarm
Units:
Sets the units for VAR measurement
(kVAR or MVAR).
Threshold:
Sets the VARS threshold level in units
specified, at or above which the power pickup
event occurs. After pickup, if the VARS fall
below the specified threshold, a power
dropout event occurs.
Delay (m):
Sets the number of minutes that the VARS
must remain at or above threshold, before the
specified trip output occurs.
VA Power Alarm
Units:
Sets the units for VA measurement.
(kVA or MVA).
Threshold:
Sets the VA threshold level in units specified,
at or above which the power pickup event
occurs. After pickup, if the VA falls below
the specified threshold, a power dropout
event occurs.
Delay (m):
Sets the number of minutes that the VA must
remain at or above threshold, before the
specified trip output occurs.
Watt Demand Alarm
Units:
Sets the units for watts demand measurement.
(kW or MW).
Threshold:
Sets the watts demand threshold level in units
specified, at or above which the power demand
pickup occurs. After pickup, if the watt demand
falls below the specified threshold, a power
demand dropout event occurs. The demand
interval is set in the Demand Setting section
described later in this section.
Delay (m):
Sets the number of minutes that the watt
demand must remain at or above threshold,
before the specified trip output occurs.
VAR Demand Alarm
Units:
Sets the units for VAR demand measurement
(kVAR or MVAR).
Threshold:
Sets the VARS demand threshold level in units
specified, at or above which the power demand
pickup event occurs. After pickup, if the VARS
demand falls below the specified threshold, a
power demand dropout event occurs. The
demand interval is set in the Demand Setting
section described later in this section.
Delay (m):
Sets the number of minutes that the var demand
must remain at or above threshold, before the
specified trip output occurs.
Effective Date: 12/05
FP-5000
For more information visit:
Effective Date: 12/05
VA Demand Alarm
Units:
Sets the units for VA demand measurement.
(kVA or MVA).
Threshold:
Sets the VA demand threshold level in units
specified, at or above which the power demand
pickup event occurs. After pickup, if the VA
demand falls below the specified threshold, a
power demand dropout event occurs. The
demand interval is set in the Demand Setting
section described later in this section.
Delay (m):
Sets the number of minutes that the VA demand
must remain at or above threshold, before the
specified trip output occurs.
Current Demand Alarm
Pickup:
Sets the current demand pickup level, at or above
which the current pickup event occurs. After
pickup, if the current demand falls below the
specified pickup, a current demand dropout
event occurs. The demand interval is set in the
Demand Setting section described later
in this section.
Delay (m):
Sets the number of minutes that the current
demand must remain at or above threshold,
before the specified trip output occurs.
NOTE: Check the Demand Logging interval. The delay for alarm
starts after the demand is logged, and the demand remains
at or above threshold for the time specified in the setting
delay for alarm. For example if the demand interval is set to
15 minutes and the delay for the demand alarm is set to 15
minutes, the system alarm pickup event occurs after 30
minutes.
I THD Alarm
Threshold:
Sets the current THD magnitude threshold
level, at or above which the current THD
pickup event occurs. After pickup, if the
current THD magnitude falls below the
specified threshold, a current THD dropout
event occurs.
Delay(s):
Sets the number of seconds that the current
THD magnitude must remain at or above
threshold, before the specified trip
output occurs.
V THD Alarm
Threshold:
Sets the voltage THD magnitude threshold
level, at or above which the voltage THD
pickup event occurs. After pickup, if the
voltage THD magnitude falls below the specified
threshold, a voltage THD dropout event occurs.
Delay(s):
Sets the number of seconds that the voltage
THD magnitude must remain at or above
threshold, before the specified trip output occurs.
Breaker Alarm
# of Operations:
The FP-5000 counts the number of breaker
operations. A breaker operation is counted
when the breaker is opened after being closed
for 3 cycles based on the state of the 52a and/
or 52b contact inputs. This setting is used to
www.eatonelectrical.com
IL17569C
Page 5-49
Page 5-49