Eaton Cutler-Hammer FP 5000 Instruction Leaflet page 61

Protective relay
Hide thumbs Also See for Cutler-Hammer FP 5000:
Table of Contents

Advertisement

IL17569C
Page 5-6
Effective Date: 12/05
Table 5.2 Protection (continued)
50P-2 PH IOC 2
Phase Overcurrent Element #2
Setting
Pickup:
Select current pickup value in per
unit values (x I
Delay (c):
Select delay time in cycles
Direction:
Select direction
IX Measured OC: Independent fourth CT time overcurrent (51X) and instantaneous (50X-1 & 50X-2) device settings
Display Setting
Description
51X IX TOC Curve Fourth CT Time Overcurrent Curve
Setting (Uses gnd CT ratio)
Shape:
Select curve characteristic shape
Reset:
Select curve reset characteristics
Direction:
Select direction
Fourth CT Time Overcurrent Pickup
51X IX TOC
and Time Multiplier Settings
Setting
Pickup:
Select current pickup value in per
unit values (x I
Time Mult:
Select Time Multiplier
Fourth CT Overcurrent Element #1
50X-1 IX IOC 1
Setting
Pickup:
Select current pickup value in per
unit values (x I
Delay (c):
Select delay time in cycles
Direction:
Select direction
Fourth CT Overcurrent Element #2
50X-2 IX IOC 2
Setting
Pickup:
Select current pickup value in per
unit values (x I
Delay (c):
Select delay time in cycles
Direction:
Select direction
Page 5-6
FP-5000
0.1 to 20.0
)
(0.01 increments)
nom
0 to 9999 cycles
(1 cycle increments)
Forward, Reverse, Both
Setpoint Range/
Value Selection
IT, I2T, I4T, FLAT, MOD,
VERY, XTRM, IECA, IECB,
IECC
Inst, Calc, T Delay
Forward, Reverse, Both
0.1 to 4.0
)
(0.01 increments)
nom
0.05 to 10.0
(.01 increments)
0.1 to 20.0
)
(0.01 increments)
nom
0 to 9999 cycles
(1 cycle increments)
Forward, Reverse, Both
0.1 to 20.0
)
(0.01 increments)
nom
0 to 9999 cycles
(1 cycle increments)
Forward, Reverse, Both
For more information visit:
3.00
or Disable
pu
15
Both
Default
Setting
XTRM
Calc
Both
0.50
or Disable
pu
1.00
1.00
or Disable
pu
60
Both
2.00
or Disable
pu
6.00
Both
www.eatonelectrical.com
5.5.2.1
8.3
Selected
Refer to
Value
Sec. #
5.5.2.2 8.3
13.4
5.5.2.2
8.3
5.5.2.2
8.3
5.5.2.2
8.3
Effective Date: 12/05

Advertisement

Table of Contents
loading

Table of Contents