Interface bit memory attribute
Bit(s):
Called:
0
Link status
1
Half duplex / full duplex
2 to 4
Negotiation status
5
Manual setting requires re-
set.
6
Local hardware fault
7 to 31
Reserved
Interface counter (STRUCT from):
Designation
In Octets
In Ucast Packets
In NUcast Packets
In Discards
In Errors
In Unknown Protos
Out Octets
Out Ucast Packets
Out NUcast Packets
Out Discards
Out Errors
PN/MF Coupler
Hardware Installation and Operating Manual, 07/2020, A5E50018670-AA
Definition
Specifies whether the IEEE 802.3 communication interface is connected to an
active network:
0 = Inactive link.
1 = Active link.
Specification of the link status depends on the implementation.
Indicates the currently used duplex mode:
0 = Interface runs at half duplex.
1 = Interface runs at full duplex.
Note that the value of the half duplex / full duplex is undefined when the link
status bit memory is 0.
Specifies the status of the link autonegotiation:
0 = Ongoing autonegotiation.
1 = Autonegotiation and speed measurement failed. Use of default values for
speed and duplex.
2 = Autonegotiation failed, but speed was measured. Duplex was faulty.
3 = Speed and duplex negotiated successfully.
4 = Autonegotiation not attempted. Forced speed and duplex.
0 = Interface can automatically activate changes to link parameters (autonegoti-
ate, duplex mode, interface speed).
1 = Device requires that a reset service is output at its Identity object so that the
changes will become effective.
0 = Interface does not detect a local hardware fault.
1 = Local hardware fault detected.
Set to 0.
Data type
Attribute description
UDINT
Octets received at the interface
UDINT
Unicast packets received at the interface
UDINT
Non-Unicast packets received at the interface
UDINT
Incoming packets received at interface but discarded
UDINT
Incoming packets containing errors (excluded In Discards)
UDINT
Incoming packets with unknown protocol
UDINT
Octets transmitted by the interface
UDINT
Unicast packets transmitted by the interface
UDINT
Non-Unicast packets transmitted by the interface
UDINT
Outgoing packets discarded
UDINT
Outgoing packets containing errors