Technical specifications
8.2 Technical specifications PN/MF Coupler (6ES7158-3MU10-0XA0)
Article number
Diagnostics indication LED
•
RUN LED
•
ERROR LED
•
MAINT LED
Monitoring of the supply voltage (PWR-LED) Yes; green PWR LED
•
•
NS LED
•
MS LED
•
IO LED
•
Connection to network LINK (green)
Potential separation
between supply voltage and electronics
between Ethernet and electronics
Isolation
Isolation tested with
Standards, approvals, certificates
network separator in accordance with IEC
61784-3-3
Network loading class
Security level
Ambient conditions
Ambient temperature during operation
•
min.
•
max.
Altitude during operation relating to sea level
•
Installation altitude above sea level, max.
Mechanics/material
Strain relief
Dimensions
Width
Height
Depth
Weights
Weight, approx.
128
6ES7158-3MU10-0XA0
Yes; green LED
Yes; red LED
Yes; Yellow LED
Yes; green/red LED
Yes; green/red LED
Yes; red-green-yellow LED
Yes; 2x green link LEDs on BusAdapter
Yes; to power input 2
Yes
707 V DC (type test)
Yes
3
According to Security Level 1 Test Cases V1.1.4
-30 °C; No condensation
60 °C; = Tmax for horizontal installation; for verti-
cal installation Tmax = 50 °C
5 000 m; restrictions for installation altitudes > 2
000 m, see section "Climatic and mechanical
environmental conditions"
Yes; Optional, for RJ45 and FC BusAdapter only
100 mm
117 mm
74 mm; with mounting rail
200 g; without BusAdapter
Hardware Installation and Operating Manual, 07/2020, A5E50018670-AA
PN/MF Coupler