Siemens SIMATIC 6ES7158-3MU10-0XA0 Hardware Installation And Operating Manual page 19

Bus couplers pn/mf coupler
Table of Contents

Advertisement

Product overview
2.3 Properties
Properties via PROFINET IO
• Data exchange in total of maximum 1440 bytes of input data and 1440 bytes of output
data
• Integrated switch on both sides with 2 ports
• Supported Ethernet services: ping, arp, SNMP, LLDP
• Port diagnostics
• Port disabling
• Device replacement without removable medium/programming device
• Firmware update via PROFINET IO
• Prioritized startup
• Media redundancy MRP
Properties via EtherNet/IP
• I/O communication with scanner
• Configuring from the user program
• Read diagnostics (interrupts are not supported)
• Normative CIP objects
• Reset PN/MF Coupler to factory settings
• Diagnostics bit in data status of cyclic I/O data per submodule
Accessories
You order the following accessories separately:
• SIMATIC BusAdapter
• Strain relief
• Labeling strips
• Reference identification label
You can find a detailed list of available accessories in the appendix Article numbers and
accessories (Page 130).
18
Hardware Installation and Operating Manual, 07/2020, A5E50018670-AA
PN/MF Coupler

Advertisement

Table of Contents
loading

Table of Contents