PROFINET IO
5.2 Configuring, parameter assignment and commissioning with PROFINET IO
5.2.3

Assignment of the modules

Introduction
You configure the PN/MF Coupler by configuring both sides separately.
You configure the network side X1 for EtherNet/IP with MFCT (Page 60) and network side X2
for PROFINET with GSD file in STEP 7 (Page 41).
The assignment of the modules is shown in the following table only from network side 1 (X1)
to network side 2 (X2). It is also possible to swap the network sides.
Table 5- 3
Modules network side 1 (X1)
Output module (OUT)
Input module (IN)
PROFIsafe IN/OUT
Only for PROFIsafe communication
1
The data length of the respective IO module must be the same for both sides. If you configure
an "IN 16 Byte+DS" on network side X1, for example, you must configure "OUT 16 Byte" for
network side X2.
PROFIsafe module
You have to observe the following for "PROFIsafe IN/OUT":
• You may only use safety-related communication for "PROFIsafe IN/OUT".
• The data status byte becomes obsolete. The validity of the coupled user data is
guaranteed by the mechanisms of the safety-related communication.
• The safety-related communication with "PROFIsafe IN/OUT" is only possible between
S7-1200/1500 F-CPUs.
We recommend that you do not use the respective modules for other applications due to the
missing data status byte (DS).
40
Assignment of the modules in the "IO Modules" module operating mode
1
Hardware Installation and Operating Manual, 07/2020, A5E50018670-AA
Assigned IO modules network side 2 (X2)
Input module (IN)
Output module (OUT)
PROFIsafe IN/OUT
1
PN/MF Coupler