General Description

2
The SARGENT Harmony Series IDP-H1 Mortise Lock is designed to interface with Wiegand Electronic
Access Control (EAC) panels. The reader requires 12VDC for power and is available with 125kHz HID proximity
technology. The H1 technology is backed by SARGENT Grade 1 hardware.
The mortise lock includes both Request to Exit (RX) and door position monitoring inside the lock body.
Featuring EcoFlex™ technology*, the H1 mortise lock is field-configurable to fail-safe or fail-secure and operates
from 12-24VDC. Weather seal gaskets are also included for outside use on exterior door applications only.
The Harmony H1 reader provides visual (LED) and audible indication of lock state (locked/unlocked).
This product offers an Integrated Door Position Switch in the mortise lock body. The magnetic switch is wired
in series with the latchbolt (LX) and auxiliary bolt (AX), offering added security and improved aesthetics.
*Sargent Manufacturing Company (New Haven, CT) 2015 U.S. Patents D601,001S; D601,002S; D601,003S; D602,762S; Patent Pending
HID and Edge are trademarks or registered trademarks of HID Global Corporation.

Hardware Specifications

3
Latch - Stainless steel 3⁄4" projection one-piece
Deadbolt - One-piece hardened stainless steel
Guardbolt - Stainless steel, non-handed
Handed - Easily field reversible without opening case
Case - 12 gauge heavy duty wrought steel
Outside lever controlled by any 125kHz HID
proximity credential
Inside lever provides RX signal and retracts latch
and deadbolt
Electrical Specifications
4
12/24VDC System
Reader Draw = 140mA @12VDC
Actuator Draw = 15mA continuous
Maximum (2) locks per 1 Amp power supply
(1/2 Amp peak current draw)
The H1 reader requires 12VDC for power.
As the lock accepts 12-24V, a 12V power supply
is recommended to support both the lock and
reader with a single power supply.
Total
One-Way
Length of
Wire Run (ft)
1/4A
1/2A
100
20
18
150
18
16
200
16
14
250
16
14
300
16
12
400
14
12
500
14
10
750
12
10
1,000
10
1,500
10
A8132C • 800-810-WIRE (9473) • www.sargentlock.com
Wire Gauge Charts
Load Current @ 12VDC
3/4A
1A
1-1/4A
1-1/2A
2A
16
14
14
12
12
14
12
12
12
10
12
12
10
10
12
10
10
10
12
10
10
10
10
Door position switch (DPS) within lock body
Magnetic switch is wired in series with the latch-
bolt (LX) and auxiliary bolt (AX)
Maximum 1/4" gap allowed between door
and strike
Locks furnished for 1-3/4" doors. Other door
thicknesses require confirmation with factory.
UL and CUL listed for use on Fire Doors
Wire from EAC panel to door must be shielded
with drain terminated at EAC Panel controller
McKinney
Electric
Total
One-Way
Length of
3A
Wire Run (ft)
1/4A
1/2A
10
100
24
20
150
22
18
200
20
18
250
18
16
300
18
16
400
18
14
500
16
14
750
14
12
1,000
14
10
1,500
12
10
3
Wiegand Access
Control System
Hinge
Harmony
Series H1 Patented
Load Current @ 24VDC
3/4A
1A
1-1/4A
1-1/2A
2A
18
18
16
16
14
16
16
14
14
12
16
14
14
12
12
14
14
12
12
12
14
12
12
12
10
12
12
10
10
12
10
10
10
10
10
3A