Typical Harmony Mortise Application Diagram (12/24VDC System)
DIAGRAM #2 – MODE 2: LED WIRE TIED TO GROUND = GREEN LED 'ON' WHEN POWERED
Standard Application Shown - For Alternative Applications Contact 1-800-810-WIRE (9473)
Reader Electronics Requires 12VDC Filtered and Regulated
12 Conductor
ElectroLynx Harness
From McKinney
Strike
(with magnet)
H1 Harmony Series
Max. gap
between door &
strike is 1/4"
12/24VDC System
Reader Draw = 140mA @12VDC
Actuator Draw = 15mA continuous
Maximum 2 locks per 1 Amp power supply (1/2 Amp peak current draw)
The H1 reader requires 12VDC for power.
As the lock accepts 12-24V, a 12V power
supply is recommended to support both the
lock and reader with a single power supply.
QC12 Electric
Hinge From
McKinney
NOTE:
If your lock is configured with End of Line Resistors,
reference instruction sheet A8191 for the wiring of
RX & DPS outputs.
*IMPORTANT: Pin 7 must be tied to earth ground in the access control panel.
Failure to follow proper ESD safe grounding procedures could lead to equipment failure.
Harmony Series IDP-H1 Mortise Lock
H
120 VAC
Input
12/24VDC
READER NEG - Black, 1
READER POS - Red, 2
DATA 1 - White, 3
DATA 0 - Green, 4
RX (NO/NC) - Orange, 5
RX (COM) - Blue, 6
*EGND- Brown, 7
LED - Yellow, 8
LOCK NEG - Violet, 9
LOCK POS - Gray, 10
DPS (NC) - Pink, 11
DPS (COM) - Tan, 12
16
A8132C • 800-810-WIRE (9473) • www.sargentlock.com
Lock body
N
G
Power Supply
(By Others)
-
+
(-)
12VDC
(+)
DATA 1
DATA 0
RX
Use (NC) for
RX
Fail Safe
Operation
DPS
DPS
(NO) Fail
Secure
Operation
Electronic
Access
Control
Panel
(By Others)
Lock Relay