Ventilation And Cooling - GE 8 Series Operating Manual

Table of Contents

Advertisement

5.5

VENTILATION AND COOLING

Fig. 5.5-1 Installation on plain floor
The heat produced by the UPS is transferred to the environment by its ventilation.
Cooling air enters the cabinets through the air inlet (grids) located at the bottom and exhausted through
the outlet on the roof.
A suitable ventilation or cooling system must be installed to extract the heat from the UPS room.
NOTE !
Insufficient space on both sides of the UPS in respect to the wall can cause a
dangerous increase of the internal operating temperature.
Do not put anything on the top of the cabinet.
If the UPS is placed on a raised floor, the airflow for UPS cooling should enter from underneath the UPS,
through the appropriate aperture on the raised floor.
If the UPS runs in a dusty environment, we recommend strongly to install filters on the air inlet of the
UPS room.
In this case it should be considered that these filters can cause reduced speed at the air inlet.
The size of the air inlet has therefore to be dimensioned accordingly.
Contact your Local Distributor or one of the Service Centre, which will help you to find valuable
solutions.
The below table indicates the heat dissipation at full load at PF = 0.8 lag. and charged battery, up to
1000 m (3280 ft) altitude, for cooling air 25°C (77°F) to 30°C (86°F).
UPS rating
SitePro 10 kVA
SitePro 15 kVA
SitePro 20 kVA
SitePro 30 kVA
SitePro 40 kVA
Modifications reserved
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Losses
VFI
SEM
1.15 kW
0.20 kW
1,61 kW
0.46 kW
2.14 kW
0.64 kW
2.73 kW
0.54 kW
3.36 kW
0.72 kW
Fig. 5.5-2 Installation on raised floor
Cooling air flow
VFI
340 m
/h
3
470 m
/h
3
625 m
/h
3
800 m
/h
3
980 m
/h
3
Operating Manual SitePro 10-15-20-30-40 kVA / S8
SEM
60 m
/h
3
135 m
/h
3
190 m
/h
3
160 m
/h
3
210 m
/h
3
Page 25/99

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents