Testing Wrist Strap Grounding Cords - Nortel DMS 100 Series Maintenance Manual

Remote switching center multi-access
Hide thumbs Also See for DMS 100 Series:
Table of Contents

Advertisement

12-24 RSC-M routine maintenance procedures

Testing wrist strap grounding cords

Application
Use this procedure to verify that the level of resistance of wrist strap grounding
cords is correct. The level must be low enough to allow static electricity to
discharge from the body of the user. The level must be high enough to prevent
electrocution. Electrocution occurs if the equipment develops a short-circuit
while the user wears the wrist strap.
Interval
Perform this procedure in one month intervals.
Common procedures
There are no common procedures.
Action
This procedure contains a summary and a list of steps. Use the flowchart to
review the procedure. Follow the steps to perform the procedure.
297-8223-550 Standard 04.02 November 2000