Nortel DMS 100 Series Maintenance Manual page 213

Remote switching center multi-access
Hide thumbs Also See for DMS 100 Series:
Table of Contents

Advertisement

RCO2 0
Please confirm ("YES", "Y", "NO", or "N"):
If
the system prompts you to confirm a warm SWACT
the system rejects the SWACT
7
To confirm the command, type:
>YES
and press the Enter key.
Example of a MAP response:
Unit0:
Unit1:
RCO2 0
If the MAP response is
SWACT passed
other
8
A maintenance flag (Mtce) can appear, that indicates system-initiated
maintenance tasks are in progress. Wait until the flag disappears from the
status lines for both RCO2 units before you proceed to the next step.
At the cabinet
Place a sign on the active unit that bears the words Active unit-Do not touch.
9
Do not use magnets or tape to attach this sign.
10
To manually busy (ManB) the inactive unit, type:
>BSY
and press the Enter key.
Example of a MAP response:
DMS-100 Family Remote Switching Center Multi-Access Maintenance Manual XPM11 and up
A Warm SwAct will be performed after
data sync of active terminals.
Inact SysB
Mtce
Act
ISTb
SwAct Passed
INACTIVE
RSC-M card replacement procedures
in an RSC-M
Do
step 8
step 20
6-61
NTMX76
(continued)
Do
step 7
step 21