Advertisement

At the MAP terminal
15
To return the inactive unit to service, type:
>RTS
and press the Enter key.
If the RTS command
passes
fails
16
Remove the sign from the active unit.
17
Go to the common returning a card procedure in this document.
18
This procedure is complete.
19
For additional help, contact the next level of support.
20
For additional help with a SWACT, contact the next level of support.
Note: The system can recommend the use of the SWACT command with
the FORCE option. If this condition occurs, contact office personnel to
determine if the use of the FORCE option is acceptable.