6-10 RSC-M card replacement procedures
NT6X69
in an RSC-M
(continued)
15
16
17
18
19
20
297-8223-550 Standard 04.02 November 2000
If PMRESET
fails with a card list
To load the inactive unit, type:
>LOADPM UNIT rco2_unit_no CC

and press the Enter key.

where
rco2_unit_no
is the number of the inactive RCO2 unit zero or one
If LOADPM
passes
fails
fails with a card list
Use the following information to determine the next step in this procedure:
If you entered this procedure
from
How to clear an procedure
other
To return the inactive RCO2 unit to service, type:
>RTS UNIT rco2_unit_no
and press the Enter key.
where
rco2_unit_no
is the number of the inactive RCO2 unit zero or one
If RTS
passes
fails
Send the defective cards for repair according to local procedure.
Record the date the card is replaced, the serial number of the card, and the
problems that prompted replacement of the card. Go to step 22.
Return to the procedure that directed you to this procedure. At the point
where the system produced a defective card list, identify the next damaged
Do
step 20
Do
step 16
step 21
step 20
Do
step 20
step 17
Do
step 18
step 21