Using Automatic Bit Rate Detection
Note:
Available in option software version 3102 and later.
Set F6-36 = 0 [CANopen Communication Speed = Auto-detection] to enable automatic bit rate detection and
cycle the drive power supply. When set to automatic bit rate detection, after power up the option will listen to
messages on the bus and adjust its bit rate setting automatically.
When the bit rate is found the option will enter pre-operational status and transmit a boot up message containing
the drive's node ID. The option will not send any messages until the bit rate is detected.
As long as the automatic bit rate detection is in progress, the RUN and ERR LEDs on the option will flicker
alternately.
Note:
• There must be bus traffic that the SI-S3 can listen to in order to detect the bit rate. If there is low traffic, the bit rate detection can take a
long time.
• The bit rate detected by the SI-S3 is not automatically saved. When cycling the drive power supply, the SI-S3 will do bit rate detection
again.
• In addition to the master, there must be at least one other node in the network that is set to the correct bit rate. For example, the bit rate
cannot be detected if the network consists of a master that is set up for a certain bit rate (controller) and one or more drives with the
option set to auto bit rate detection.
Node ID Setup
The node ID can be set in F6-35. The value range is 1 to 126. Each node ID may only be used once in the
network.
After changing F6-35, cycle the drive power supply to enable the changes.
Note:
When the node is set to 0, the ERR light will flash and "AEr" will appear on the drive keypad to indicate that an address setting error has
occurred.
8
Object Dictionary
Object Dictionary Overview
The Object Dictionary consists of three sections:
• Communication Profile Objects
• Manufacturer Specific Profile Objects
• Drive and Motion Profile Objects
The tables below provide an overview of the communication objects available in the SI-S3 option.
Communication Profile Objects (DS 301)
Refer to
Communication Profile Objects (DS 301) on page 31
Objects.
Index (Hex.)
1000
1001
1003
1005
1008
1009
100A
100C
100D
100E
1010
YASKAWA SIEP C730600 85D CANopen Technical Manual
Device Type
Error Register
Pre-defined Error Field
COB-ID SYNC Message
Manufacturer Device Name
Manufacturer Hardware Version
Manufacturer Software Version
Guard Time
Life Time Factor
Node Guarding Identifier
Store Parameters
for further details on Communication Profile
Name
8 Object Dictionary