6 Related Drive Parameters
Communication Cable Specifications
Use only CANopen dedicated communication cable; the Yaskawa warranty does not cover other cable types.
Option Connection Diagram
You must connect the option to the network using a 9-pin D-sub connector wired as shown in
*1
Connect the included ground wire for installations on 1000-series, GA500, and FP605 drives. The ground wire is not necessary for
installation on GA700 or GA800 drives.
Termination Resistor Connection
Both ends of a CANopen network have to be terminated with a 120 Ω resistor. As the option has no build in
termination resistor, make sure to apply a termination resistor as shown in
the last node in the network.
*1
Connect the included ground wire for installations on 1000-series, GA500, and FP605 drives. The ground wire is not necessary for
installation on GA700 or GA800 drives.
EDS Files
For easy network implementation of drives equipped with a CANopen Option, an EDS file can be obtained from:
U.S.: http://www.yaskawa.com Europe: http://www.yaskawa.eu.com Japan: http://www.e-mechatronics.com
Other areas: Check the back cover of these manuals. For questions, contact Yaskawa or a Yaskawa representative.
You can download drive manuals from the Yaskawa product and technical information website shown on the back
cover of this manual.
6
Related Drive Parameters
These parameters set the drive for operation with the option. Confirm correct parameter settings in this table
before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are represented in hexadecimal
numbers.
26
Figure 5.22 Option Connection Diagram
Figure 5.23 Termination Resistor Connection
Figure 5.23
if the CANopen Option is
YASKAWA SIEP C730600 85D CANopen Technical Manual
Figure
5.22.