4 Option Components
4
Option Components
Option
A - Communication cable connector (9 pin D-sub)
B - Option model number
C - Connector (CN5)
D - Installation hole
*1
Refer to
Option LED States on page 10
*2
Connect the included ground wire during installation. The ground wire is not necessary for installations on GA700 and GA800
drives.
Communication Connector
The CANopen Option is connected to the network using a 9-pin D-sub connector. The pin assignment is explained
in the table below.
CANopen Connector
Option LED States
Option has two LEDs that identify the option or communication status.
Option LED Status Definitions
A - 1000-Series
B - GA500, GA700, GA800
10
Figure 4.1 Option
for more information about the LEDs.
Table 4.1 Communication connector (9-pin D-sub)
Pin
Signal
1
-
2
CAN_L
3
CAN_GND
4
-
5
CAN_SHLD
6
-
7
CAN_H
8
-
9
-
-
CAN_SHLD
Figure 4.2 Option LED Labels
E - LED (RUN)
*1
F - LED (ERR)
*1
G - Ground terminal (FE) and installation hole
-
CAN_H bus line (dominant high)
CAN Ground
-
CAN shield
-
CAN_H bus line (dominant high)
-
-
CAN shield
C - FP605
YASKAWA SIEP C730600 85D CANopen Technical Manual
*2
Description