Loop Break Time Menu/Field Calibration; Figure 3.7 Flow Chart For Loop Break Time - Newport i Series Operator's Manual

Temperature & humidity controller
Hide thumbs Also See for i Series:
Table of Contents

Advertisement

3.2.8 Loop Break Time

Figure 3.7 Flow Chart for Loop Break Time

ENTER LOOP BREAK TIME MENU:
Press a
Press d
Press a
Press d
LOOP BREAK ENABLE/DISABLE SUBMENU:
Press b
Press d
Loop Break is an additional safety feature intended to monitor the rate of
change of the process value, while approaching the SP1, if on the Sensor Menu
DRRh is selected, or SP2 if °F.°C is selected. It is strictly intended as an
additional warning system, therefore its use is entirely optional. An active Loop
Break will cause the Process Value digits to blink in a rotating pattern. If the
process value reaches the set point the blinking will stop and B.TIM is
completed successfully, otherwise BR.AL Break Alarm warning will flash, and
Output 1 will be turned off.
LOOP BREAK TIME VALUE SUBMENU:
Press d
Press b & c 8) Press b and c buttons to enter a new Loop Value (0 to
Press d
Loop Break Time Value allows the user to determine the time interval in MM:SS
(from zero to 99 minutes and 59 seconds) that the Process Value changes at
least 10 counts. At the specified time interval, if the process value change is less
than the stated rate, flashing B.TIM will be displayed, the output will be de-
energized, and Alarm energized. Loop break time will be disabled when the
Process Value (PV) enters the control band.
Loop Break Alarm can work on the RH or Temperature function of the
selection made on the Sensor Menu.
1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to RDG Reading Configuration Menu.
3) Press a , if necessary, until Display advances to LOOP Loop
Break Time Menu.
4) Display advances to Loop Break Time ENBL Enable or
DSBL Disable Submenu and flashes the previous selection.
5) Scroll through the available selections: ENBL or DSBL .
6) Display shows STRD stored message momentarily and then
advances to B.TIM Loop Break Time Value Submenu.
7) Display flashes 1 st digit of previous Loop Value.
99.59).
9) Display shows STRD stored message momentarily and then
advances to R.ADJ Reading Adjust Menu.
25
It is required
that you put
the controller
in the Standby Mode
for any configuration
change other than
Set Points & Alarms.