ANALOG OUTPUT ENABLE/DISABLE SUBMENU:
Press b
Press d
If DSBL Analog Output Disabled was selected, all submenus of Analog
Output Menu will be skipped and the meter will advance to ALR2 Alarm 2
Menu. If ENBL Analog Output Enabled was selected, Output 1 would be
automatically Disabled, and reassigned as Analog Output.
CURRENT/VOLTAGE SUBMENU:
Press d
Press b
Press d
READING 1:
Press d
Press b & c 11) Enter "Reading 1" value. (Example 0000)
Press d
OUT 1:
Press d
Press b & c 14) Enter "Out 1" value. (Example 00.00)
Press d
READING 2:
Press d
Press b & c 17) Enter "Reading 2" value. (Example 100.0)
Press d
OUT 2:
Press d
Press b & c 20) Enter "Out 2" value. (Example 10.00)
Press d
The above example (also the factory default) is for 0-10 V of the entire
range of the Humidity Input and Analog Output. For 0-20 mA output you
need to set "Analog Type" to Current and OUT 2 to 20.00.
5) Scroll though the available selection until ENBL displays to
use Analog Output Retransmission (output proportional to the
input signal).
6) Display shows STRD stored message momentarily and then
advances to CURR or VoLT Submenu only if it was changed,
otherwise press a to advance to CURR or VoLT
Current/Voltage Submenu.
7) Display flashes CURR Current or VoLT Voltage.
8) Scroll through the available selection: Current or Voltage
(Example VoLT ).
9) Display shows STRD stored message momentarily and then
advances to RD1 Submenu only if it was changed, otherwise
press a to advance to RD1 Reading 1 Submenu.
10) Display flashes 1
12) Display advances to OUT.1 Out 1 Submenu.
13) Display flashes 1
15) Display advances to RD!2 Reading 2 Submenu.
16) Display flashes 1
18) Display advances to OUT.2 Out 2 Submenu.
19) Display flashes 1
21) Display advances to the ALR2 Alarm 2 Menu.
st
digit of previous "Reading 1" value.
st
digit of previous "Out 1" value.
st
digit of previous "Reading 2" value.
st
t
digit of previous "Out 2" value.
22