Reading Adjust Menu; Setpoint Deviation Menu/Field Calibration; Figure 3.7 Flow Chart For Reading Adjust - Newport i8-AL Operator's Manual

I series temperature/process limit alarm controller
Table of Contents

Advertisement

3.2.8 Reading Adjust Menu

For Temperature Reading
only, not Process
Figure 3.7 Flow Chart for Reading Adjust Menu
ENTER READING ADJUST MENU:
Press a
Press d
Press a
READING ADJUST VALUE SUBMENU:
Press d
Press b & c
Press d
Reading Offset Adjust allows the user to fine tune a minor error of the
ransducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ±R.ADJ).
Reading Adjust value is adjustable between -1999 to 9999.
3.2.9 Setpoint Deviation Menu / Field Calibration
Figure 3.8 Flow Chart for Setpoint Deviation Menu / Field Calibration
ENTER SETPOINT DEVIATION MENU:
Press a
Press d
Press a
1) Press a, if necessary until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a ,if necessary, until display advances to R.ADJ
Reading Adjust Menu.
4) Display flashes first digit of previous Reading Adjust value.
5) Press b and c buttons to enter a new Reading Adjust value
(-1999 to 9999).
6) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
1) Press a, if necessary, until CNFG prompt appears.
2) Display advances to INPT Input Menu.
3) Press a, if necessary, until Display advances to SP.DV
Setpoint Deviation Menu.