6.7.3 Setpoint Limits (INIt > SFty > SP.LM)
Select Setpoint Limits (SP.LM) to set limits on the values that can be used for the all Setpoints.
Navigate to the desired setting. Settings include the following:
SP.Lo – Set the minimum possible Setpoint value
SP.HI – Set the maximum possible Setpoint value
Select the desired setting.
Set the Setpoint limit value.
Confirm the value.
6.7.4 Loop Break Timeout (INIt > SFty > LPbk)
Select the loop break (LPbk) parameter. When enabled, this parameter specifies the amount
of time in Run Mode without a change in input value that would signify a sensor malfunction.
For example, if there were a problem in a thermocouple, the input would not change over
time.
Navigate to the desired setting. Settings include the following:
dSbL – No loop break timeout protection (factory default)
ENbL – Set loop break timeout value
Select the indicated setting.
If ENbL, Set the loop break timeout value in minutes and seconds (MM.SS)
Confirm the value.
6.7.5 Open Circuit (INIt > SFty > o.CRk)
Select the open circuit (o.CRk) parameter. When o.CRk is enabled, the unit will monitor
Thermocouples, RTD, and Thermistors for an open circuit condition.
Navigate to the desired setting. Settings include the following:
ENbL – Open circuit conditions will stop the program and display oPEN (factory
default)
dSbL – No open circuit protection (may be necessary when using high impedance
infrared thermocouples or thermistors).
Confirm the value.
Reference Section: Initialization Mode (INIt)