READING ADJUST SUBMENU:
Press d
Press b & c 11) Press b and c buttons to enter a new Reading Adjust value
Press d
Reading Offset Adjust
For Relative Humidity, the controller allows the user to fine tune a minor error of
the transducer, however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ).
R.ADJ is adjustable between -19.99 to 99.99
SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:
Press d
Press b
Press d
Setpoint Deviation Submenu, if "enabled", allows changes to Setpoint 1 to be
made automatically to Setpoint 2. This mode is very helpful if the Process Value
changes often. In Setpoint Deviation Mode, set SP2 a certain number of degrees
or counts away from SP1 - this relation remains fixed when SP1 is changed. For
instance: Setting SP1=200 and SP2=20 and enabling SP.DV means that the
absolute value of SP2=220. Moving SP1 to 300, the absolute value of SP2
becomes 320.
10) Display flashes 1 st digit of previous reading adjust value.
(-1999 to 9999).
12) Display shows STRD stored message momentarily and then
advances to SP.DV Setpoint Deviation Menu.
13) Display advances to Setpoint Deviation ENBL Enable or
DSBL Disable Submenu and flashes the previous selection.
14) Scroll through the available selections: ENBL or DSBL .
15) Display shows STRD stored message momentarily and
then advances to OUT1 Menu.
26