3.2.7 Alarm 2
This unit is equipped with two physical outputs that can only be configured as
follows: Alarm 1 & Alarm 2, Alarm 1 & Output 2, Output 1 & Alarm 2, Output 1
& Output 2, Analog Out 1 & Alarm 2, Analog Out 1 & Output 2. Analog Out
available only if Analog Output Option board is factory installed. Alarm 2 only
works for Temperature, not Humidity.
Alarm must be DISABLED if Ramp is ENABLED.
ENTER ALARM 2 MENU:
Press a
Press d
Press a
Press d
ALARM 2 ENABLE/DISABLE SUBMENU:
Press d
The remaining Alarm 2 menu items are identical to Alarm 1 Menu. Modifying
Alarm Settings will not reset the instrument.

Figure 3.6 Flow Chart for Alarm 2

1) Press a , if necessary, until CNFG prompt appears.
2) Display advances to RDG Reading Configuration Menu.
3) Press a , if necessary, until Display advances to ALR2 Alarm 2 Menu.
4) Display advances to Alarm 2 ENBL Enable or DSBL Disable
Submenu.
5) Display flashes previous selection. Press b until ENBL displays
to use Alarm 2.
6) Display shows STRD stored message momentarily and then
advances to ABSo only if it was changed, otherwise press a to
advance to ABSo Absolute/Deviation Submenu.
If DSBL Alarm 2 Disabled was selected, all submenus of Alarm 2 will
be skipped and meter advances to LOOP Loop Break Time Menu. If
ENBL Alarm 2 Enabled was selected, Output 2 will automatically
Disabled, and reassigned as Alarm 2.