Configuring with Studio 5000 Logix Designer

3.3 Creating a Studio 5000 Logix Designer project

3.3
Creating a Studio 5000 Logix Designer project
The modules can be integrated into Rockwell automation systems using Studio 5000
Logix Designer. The connection is via Ethernet/IP. Following this, you can configure the
RF600 reader using WBM while you control the work with the module using the add-on
instructions of Studio 5000 Logix Designer.
Requirement
The module is connected, has started up and an IP address has been assigned to the
device. The Studio 5000 Logix Designer was started.
Procedure
Follow the steps below to create a new project:
1. Start the Studio 5000 Logix Designer.
2. Create a new project.
Select the controller you are using and configure the project properties.
3. Add an Ethernet/IP module if necessary.
4. Right-click on "Ethernet" in the "Controller Organizer > I/O Configuration" area.
5. In the shortcut menu, select the menu command "New Module...".
The input screen "Select Module Type" is opened.
6. Select the module (e.g. "RF600") and click "Create".
The input screen "New Module" opens.
7. Enter the name of the device in the "Name" text box.
8. Enter the IP address of the device in the "IP address" text box.
9. Click the "Change" button.
The input screen "Module Definition" opens.
10. In the "Size" box change the data word size from "SINT" to "INT".
11. Confirm your entry with "OK".
12. Confirm with "OK".
12
Ident profile, Add-on instruction for Rockwell systems
Function Manual, 07/2020, C79000-G8976-C410-04