Diagnostics and error messages
5.1 Error messages from the Ident profile / Ident instructions
Error mes-
Description
sage
(hex)
0xE2FE0100
Field disturbance on reader
Possible causes:
The reader is receiving interference pulses from the environment.
External interference field. The interference field can be detected with the "inductive field indi-
cator" of the mobile reader.
The distance between two readers is too small and does not correspond to the configuration
guidelines.
The connecting cable to the reader is defective or too long or does not comply with the specifi-
cation.
Too many transmit errors
The transponder was unable to receive the command or the write data from the communications
module correctly even after several attempts.
The transponder is positioned exactly in the limit area of the transmission window.
Data transmission to the transponder is being affected by external interference.
CRC sending error
The transponder reports CRC errors frequently (transponder is positioned in the limit area of
the reader; transponder and/or reader has a hardware defect).
Only during initialization: CRC error on receipt of acknowledgment from transponder (cause as for
field interference on the reader).
When formatting, the transponder must be in the transmission window of the reader; otherwise, a
timeout error will occur, i.e.:
The transponder is located exactly in the limit area of the transmission window.
The transponder is defective and consumes too much power.
The EEPROM transponder was incorrectly configured by "FORMAT".
RF600:
No ETSI channel is available.
An incorrect communication standard was selected in the "INIT" command.
The expert parameter is incorrect.
The performance check of the ETSI wireless profile is faulty.
Freeport: Negative acknowledgment or bad frame from the reader
0xE2FE0200
More transponders are located in the transmission window than can be processed at the same
time by the reader.
There is more than one transponder in the transmission window.
0xE2FE8100
There is no transponder with the required EPC ID/UID in the transmission window or there is no tran-
sponder at all in the antenna field.
0xE2FE8200
The requested data is not available.
0xE2FE8300
CRC error in reader-transponder communication.
0xE2FE8400
The selected antenna is not enabled.
0xE2FE8500
The selected frequency is not enabled.
0xE2FE8600
The carrier signal is not activated.
0xE2FE8700
There is more than one transponder in the transmission window.
0xE2FE8800
General radio protocol error
106