Figure 4-38 Disengaging The Power Distribution Board - Sun Microsystems Netra 440 Service Manual

Hide thumbs Also See for Netra 440:
Table of Contents

Advertisement

15. Disengage the power distribution board from the motherboard.
a. Using a Phillips screwdriver, loosen the two captive screws that secure the base
of the power distribution board to the server (
b. Pull on the ejector latches to unseat the power distribution board from the
motherboard (
Leave the power distribution board in its bay, but disconnected from the
motherboard.
Disengaging the Power Distribution Board
FIGURE 4-38
112
Netra 440 Server Service Manual • August 2004
).
FIGURE 4-38
SCC
).
FIGURE 4-38