Note
When providing a separate output supply voltage to a group of 8 outputs, the
supply voltage common must be terminated on the base module using the 0 V
potential of the WAGO-I/O-SYSTEM 752 (blue terminal block).The entire
current load is applied to the common terminal connection.
If more than 6 Amps is applied to the common terminals, separate terminal
blocks should be used. Connect all common connections to the terminal
blocks, and then connect the 752 common to the terminal blocks. This row of
terminal blocks will be wired back to the source common of the supply poten-
tial.

4.2.5 Connection of the Output Signals

The output signal terminals are identified by the imprint "OUTPUT" on the
base module.
Two terminals are available for each digital output. The terminals for one out-
put are shown superimposed in Fig. 4-11.
Color
Fig. 4-11: Actuator connection
The positive connection of an actuator is wired to the grey output terminal
block. The negative connection of an actuator is wired to the blue output ter-
minal block.
Color
Fig. 4-12: Examples of an actuator connection
Fieldbus Dependent I/O Module
INTERBUS
Vertical connection group for one channel
Output
grey
1
2
3
blue
0 V
33 34 35
grey
1
2
3
blue
33 34 35
9
10 11
41 42 43
Installation
• 17
g1xxx07e
g1xxx09e