WAGO 752 Owner's Manual page 12

Fieldbus dependent i/o module interbus
Hide thumbs Also See for 752:
Table of Contents

Advertisement

8 •
Technical Data
Inputs
Number of inputs
Input
Wire connection
Signal voltage (0)
Signal voltage (1)
Time constant
Insulation
electronics/field side
Outputs
Number of outputs
Rated voltage
Rated current
– max. per output
– max. per group (8 outputs)
– max. per module 16 DO
Leakage current
Short circuit protection
Max. operating frequency
(without bus)
– resistive load
– inductive load
Insulation
electronics/field side
Diagnosis
Feeding
Degree of Protection
Degree of protection according to
EN 60 529
Conformity and Certification
Conformity labelling
UL
16
in accordance with EN 61131-2, type 1
for 3 conductors
DC –3 V ... +5 V
DC 15 V ... 30 V
5 ms
none
16
DC 24 V
500 mA
4 A
8 A
< 2 mA
electronic, automatic restart
1 kHz
utilization category DC 13, equals 6 Hz
none
Short circuit display by LED (OVERLOAD) for the
entire module; signaling via bus for 4 outputs each
all through supply terminal blocks 24 V, 0 V,
with plugged jumpers
in groups via supply terminal blocks for 8 outputs
each
IP 20 protection against physical contact with stan-
dard test probes
CE
E175199, UL 508
Fieldbus Dependent I/O Module