4. Scroll through the pick list until you come to 'Net Input Flag 1' and press [ENTER]. This setting
uses the first 16 bits of the possible 64 bits.
Now the corresponding bits from the drctry.plus file can be used in the SOP, as shown below:
;Network1Flag0_I Use bit 0 for Stop bit
;Network1Flag1_I Use bit 1 for Run Forward bit
RunRequest_O = /Network1Flag0_I * Network1Flag1_I;Run drive using
bit 1,stop using bit 0
5. Select 'Net Input Flag 2' to use the second set of 16 bits, and so on.
Note
By choosing 'Data to Drive 03' as the write register, the PLC must now send 0x02 in register
'Data to Drive 03' to run the drive.
To stop the drive, the PLC must send 0x01 in register 'Data to Drive 03'.
The pick list variables and the corresponding programmable input bits are found in the following
tables for network 1 and 2, respectively.

Table 6-5

Pick list variable in 'Data to Drive Reg nn' menus Related Drctry.plus bits
Net Input Flag 1
Net Input Flag 2
Net Input Flag 3
Net Input Flag 4
Table 6-6
Pick list variable in 'Data to Drive Reg nn' menus Related Drctry.plus bits
Net Input Flag 1
Net Input Flag 2
Net Input Flag 3
Net Input Flag 4
NXGPro+ Communication Manual
Function Manual, AA, A5E50226719
Network 1: Programmable input bits (parameter ID 9603-9664)
Network 2: Programmable input bits (parameter ID 9703-9764)
Ethernet / IP Communication
6.3 Software Programming
Network1Flag0_I ~ Network1Flag15_I
Network1Flag16_I ~ Network1Flag31_I
Network1Flag32_I ~ Network1Flag47_I
Network1Flag48_I ~ Network1Flag63_I
Network2Flag0_I ~ Network2Flag15_I
Network2Flag16_I ~ Network2Flag31_I
Network2Flag32_I ~ Network2Flag47_I
Network2Flag48_I ~ Network2Flag63_I
85