6.5.6

Setup Example

Task
Set up network to indicate the following drive outputs on the PLC:
• General Status
• Motor speed
• Output Power
• Number of Active Faults
Procedure (Task Example)
Refer to table Correspondence between Drive Parameter ID and Communication Protocol
Address in section Parameter Assignment / Addressing to establish whether an address or
register is changeable.
• General Status and Motor Speed Indication:
1. "Data from Drive 01' is not changeable; it is set to indicated general status.
Action: No action is required.
2. 'Data from Drive 02' is not changeable; it is set to indicate motor speed.
Action: No action is required.
3. 'Data from Drive 03' is changeable.
Action: Set to indicate output power
4. Determine that the corresponding parameter ID is 9403.
Action: Enter parameter ID 9403.
5. Choose 'output power' from the pick-list.
Action: Output power will be sent to the PLC using register 'Data from Drive 03'.
• Number of Active Faults Indication
1. The table shows that 'Data from Drive 04' is changeable.
Action: Set to indicate the number of active faults.
2. Determine that the corresponding parameter ID is 9404.
Action: Enter parameter ID 9404.
NXGPro+ Communication Manual
Function Manual, AA, A5E50226719
Ethernet / IP Communication