Modbus Ethernet Communication
5.4 Parameter Assignment/Addressing
Network 2 Parameters
Table 5-17
Network 2: Configure Menu (9914)
Parameter
ID
Network 2 Type
9915
Table 5-18
Network 2: Configure Parameters Menu (9916)
Parameter
ID
Velocity Units
9924
Demand Scalar
9926
Aux Demand Scalar
9927
Network Timeout
9935
IP Address
9936
Subnet Mask
9937
Gateway Address
9938
Table 5-19
Network 2: Register Data from Drive Menu (9500)
Parameter
Data From Drive 01
Data From Drive 02
Data From Drive 03 to 64
66
Unit
Default
Min Ma
None
Unit
Default
Min
%
1
-125
1
-125
0
0
172.16.20
.17
255.255.0
.0
172.17.1.
1
ID
Unit
Default
9501
General Sta‐
tus
9502
Motor Speed
9503 to
None
9564
Description
x
Designate the type of external network connected to the
drive:
•
None
•
Modbus
•
DeviceNet
•
Profibus
•
Ethernet Modbus
•
ControlNet
•
Ethernet I/P
Max
Description
Designate the units for velocity values from the drive:
•
%
•
RPM
•
Hz
125
Set the scalar for input demand reference from the net‐
work.
125
Set the auxiliary scalar for input demand reference from
the network.
65535 Set the timeout for network determined to be non-re‐
sponsive.
Set the system TCP-IP address.
Set the system TCP-IP subnet mask.
Set the system TCP-IP address gateway address.
Min
Max
Description
Register data from drive parameter 1.
Register is not programmable.
Register data from drive parameter 2.
Register is not programmable.
Register data from drive parameters 3 to 64.
Registers are programmable.
NXGPro+ Communication Manual
Function Manual, AA, A5E50226719