Pick-List Variable Tables - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Medium-voltage drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Table 9-17
Network 2: Register Data to Drive Menu (9700)
Parameter
Data To Drive Reg 01
Data To Drive Reg 02
Data To Drive Reg 03 to 64
9.4.4

Pick-list Variable Tables

Table 9-18
Data from Drive Pick-list Variables
Name
Manual ID
None
None
Man Id
None
General Status
2001
Motor Voltage
2100
Total Current
2190
Output Power
2230
Motor Speed
2014
Speed Demand
2060
Speed Reference
2010
NXGPro+ Communication Manual
Function Manual, AA, A5E50226719
ID
Unit
Default
9701
Fixed Reg Bits
9702
Velocity De‐
mand
9703 to
None
9764
Unit
Scaling
None
None
None
None
None
None
Volts
/1
Amps
/1
KW
/1
%
/10
/1
RPM
/10
Hz
%
/100
%
/100
9.4 Parameter Asssignment / Addressing
Min
Max
Description
Register data to drive parameter 1.
Register is not programmable.
Register data to drive parameter 2.
Register is not programmable.
Register data to drive parameters 3 to 64.
Registers are programmable.
16-bit Data Type Notes
None
None
None
Refer to appendix Internal Drive Net‐
work
Bit Field
Unsigned
Unsigned
Signed
Unsigned
Unsigned
Unsigned
ControlNet Communication
Bit 0: Fault
Bit 1: Alarm
Bit 2: Running Forward
Bit 3: Running Reverse
Bit 4: Drive Ready
Bit 5: Start/Stop Control From Net‐
work
Bit 6: Speed Reference From Net‐
work
Bit 7: At Speed Reference
Bit 8: Speed In Percent
Bit 9: Speed In RPM
Bit 10: Speed In Hz
Bit 11: Reserved for future use
Bit 12: Reserved for future use
Bit 13: Reserved for future use
Bit 14: Reserved for future use
Bit 15: Reserved for future use
175