Available Id Function Commands - Siemens SINAMICS PERFECT HARMONY GH180 Function Manual

Medium-voltage drive
Hide thumbs Also See for SINAMICS PERFECT HARMONY GH180:
Table of Contents

Advertisement

Appendix
A.3 Parameter Read / Write
PTD Register
Register Function
PTD3
Write Value
PTD4
Write Value
The following table lists the available ID Function commands for use when PTD1 is set to a
"Function command" (value 41).
The table also lists the PTD and PFD usage for each parameter function.
Table A-4

Available ID Function Commands

Parameter ID
Function
1260
Autotune Stage1
1270
Autotune Stage2
2640
Reset Bypassed Cells
3510
Start Control Loop Test
3520
Stop Control Loop Test
5045
Set Current As Default
5050
Reset to Defaults
6200
Clear Event Log
6240
Alarm/Fault Log Clear
8030
Preset Hour Meter
8040
Reset Hour Meter
8060
Alarm/Fault Log Clear
8070
Reset Output KWH Meter
8074
Preset Input KWH Meter
8076
Reset Input KWH Meter
222
Value
Description
N/a
Value to be used for write parameter value command for Least
Significant 16-Bits
N/a
Value to be used for write parameter value command for Most
Significant 16-Bits
PTD Use
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
Not used
PTD3 = Value
PTD4 = Exponent
Not used
PTD3 = Value
PTD4 = Exponent
Not used
PTD3 = Value
PTD4 = Exponent
Not used
PFD Use
Not used
Not used
Not used
Not used
Not used
PFD3: 1 = Error
PFD4: Not used
Not used
Not used
PFD3: 1 = Error
PFD4: Not used
Not used
Not used
Not used
Not used
Not used
Not used
NXGPro+ Communication Manual