All rights reserved. No part of this publication may be reproduced in any material form (including photocopying or storing in any medium by electronic means or other) without the written permission of the copyright holder. SmartGen Technology reserves the right to change the contents of this document without prior notice. Software Version Date...
HAT160 ATS CONTROLLER USER MANUAL 1. OVERVIEW HAT160 ATS Controller is suitable for CB ATS of single motor. It can accurately detect 2-way-3-phase 4-wire/single-phase 2-wire voltage and judge voltage abnormal (such as, over voltage, under voltage, over frequency, under frequency and lack of phase), then control ATS after delay. When ATS switch abnormally, the controller can detect close/open failure and alarm on the front panel to ensure the correct action of ATS.
HAT160 ATS CONTROLLER USER MANUAL 3. SPECIFICATION Items Contents AC power A1N1/A2N2 supply. Operating Voltage Rated AC240V (range: AC170V~277V) Power Consumption Under rated voltage, power consumption is not more than 2VA AC Voltage Input: AC170V – AC277V (ph-N) 3-phase 4-wire AC170V –...
HAT160 ATS CONTROLLER USER MANUAL 4. PANEL DESCRIPTION 4.1 FRONT PANEL KEY FUNCTION DESCRIPTION Icon Function Description Auto/Manual mode switch; Auto/Manual Enter into lamp test status by pressing for 3s; (Setting) Enter into parameter configuration mode by pressing for 5s.
HAT160 ATS CONTROLLER USER MANUAL INDICATOR DESCRIPTION Indicators Description Lamp illuminates: 1# power normal; Lamp flashes: 1# power abnormal (over/under voltage, over/under 1# Power frequency and lack of phase); Lamp off: 1# loss of power Lamp illuminates: 2# power normal;...
HAT160 ATS CONTROLLER USER MANUAL 5. ALARM 5.1 CLOSE/OPEN FAULT ALARM In Auto mode, after the controller send a open signal, if the controller can also detect open signal when open delay ends, it will be regarded as open failure and the alarm indicator illuminates at the same time.
HAT160 ATS CONTROLLER USER MANUAL 6. CONNECTION Terminal Function Note 1# A phase 1# B phase 1# AC 3-phase 4-wire voltage input; If it is single-phase, connect A1 and N1 only, B1 and C1 hang up. 1# C phase 1#N phase...
Page 10
HAT160 ATS CONTROLLER USER MANUAL Terminal Function Note as power supply for ATS switching. If has trip function, the trip input must be connected to aux. alarm terminal. Can control ATS to switch to Breaking (OFF) position, AC voltage input.
Page 11
HAT160 ATS CONTROLLER USER MANUAL Fuse changing Programme via LINK HAT160 ATS Controller 2015-12-09 Version 1.0 Page 11 of 17...
HAT160 ATS CONTROLLER USER MANUAL 7. DEFINITION AND RANGE OF PARAMETERS Form1 Items Range Default Description Priority (1-3) 1: 1# priority 2: 2# priority 3: Spare to each other 1# Volt Abnormal (1-7) 2 (5s) 1: 1s Delay 2: 5s...
Page 13
HAT160 ATS CONTROLLER USER MANUAL Items Range Default Description 4: 8s 5: 10s 6: 15s 7: User defined(Default: 1s) 1# Volt Normal Delay (1-7) 2 (5s) 1: 1s 2: 5s 3: 10s 4: 20s 5: 30s 6: 45s 7: User defined(Default: 5s)
HAT160 ATS CONTROLLER USER MANUAL 9. TYPICAL APPLICATION CAUTION: If ATS has trip function, then it must be connected to AL port (AC Volt input). Ensure 1# and 2# A phase won’t be abnormal at the same time, otherwise the controller won’t send Close/Open signal.
HAT160 ATS CONTROLLER USER MANUAL 10. VERALL DIMENSION AND PANEL CUTOUT 10.1 CASE DIMENSION Unit: mm 10.2 CUTOUT The controller has three installation ways: panel built-in, internal 35mm slideway and internal screw mounting. Panel built-in and internal screw mounting are as below:...
HAT160 ATS CONTROLLER USER MANUAL 10.3 INSTALLATION A)Fixing Clips B) 35mm Slideway C) Screw Mounting 11. TROBLESHOOTING Symptom Possible Remedy Check connections of 1# and 2# power; Controller inoperative Check F1 or F2 fuse Check ATS; Switch not activate Check the connections between controller and ATS.