Alphanumeric Touchpad Issues; Fixed Display Touchpad Issues - GE Concord 4 Installation Manual

Hide thumbs Also See for Concord 4:
Table of Contents

Advertisement

2. Concord panels are voltage sensitive, so it's necessary to check for proper
voltage:
On hook voltage should be approximately 48-52 volts.
Off hook voltage should be approximately 6-10 volts.
Note:
The Concord panel has a built-in line voltage meter. If it does not see proper
voltage, it will not dial on a tone phone line. This does not apply to a pulse phone line.
To check proper phone line with line seizure:
1. Check the type of phone line. Concord panels work with analog phone lines or DSL
with a DSL filter inline to the panel. VOIP or digital phone lines may not work with
the panels.
2. Check that the premise's phone line is working.
3. Check that the DB-8 cord is plugged into the RJ31X/CA-38A jack.
4. Check for correct phone line wiring between the TELCO block and the RJ31X/CA-
38A jack.

Alphanumeric touchpad issues

Display shows all ************.
Touchpad is not connected to panel bus terminals or is wired incorrectly. Check and
correct wiring.
Display is blank.
• Check that panel is powered up.
• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.
• Check the touchpad brightness setting. (See Options menu on page 108.)
Touchpad buttons don't beep when pressed.
• Check for touchpad power and/or incorrect bus wiring, opens, or shorts.
• Check that key beeps option is set to on. (See the Accessory modules - bus device
settings on page 93.)

Fixed display touchpad issues

Display is lit but does not respond to key presses.
• Touchpad is not connected to panel bus terminals or is wired incorrectly. Check
and correct wiring.
• Check that touchpad is learned into panel memory.
Concord 4 Installation Manual
Chapter 4: Testing and troubleshooting
105