Specification
Power supply
Airflow Rate
External static pressure
Average
Temperature
exchange
Cooling
efficiency
Heating
Cooling
Enthalpy
exchange
efficiency
Heating
Heat exchange mode
Operating sound
Bypass mode
Normal input
Heat exchange mode
Normal input at 0 Pa external static pressure
Normal amp.
Heat exchange mode
Effective ventilation rate
Dimensions
Weight
Indoor side
Connection duct
diameter
Outdoor side
Around the unit
Unit ambient
Outdoor air
condition
Return air
Drawing number
Note:
Refer to page 85.
84
Model
Ultra-High m³ / h
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
High
Low
Ultra-High
Ultra-High
High
Low
Ultra-High
H × W × D
VAM1000HVLT
Single phase, 220 V, 60 Hz
1,000
m³ / h
1,000
m³ / h
835
Pa
220
Pa
100
Pa
70
%
66.0
%
66.0
%
69.5
%
58.0
%
58.0
%
62.0
%
74.0
%
74.0
%
76.5
%
60.0
%
60.0
%
62.5
%
68.5
%
68.5
%
72.5
dBA
42.5
dBA
38.0
dBA
34.5
dBA
42.5
dBA
38.0
dBA
34.5
W
883
W
763
W
594
W
971
A
4.04
A
3.48
A
2.72
%
90
mm
387 × 1,012 × 1,110
kg
63
 250
mm
 250
mm
–10°C to 50°CDB (80% RH or less)
–15°C to 50°CDB (80% RH or less)
–10°C to 50°CDB (80% RH or less)
3D135416
EDMMT712101
VAM1500HVLT
VAM2000HVLT
1,500
1,500
1,250
235
125
88
69.5
69.5
73.0
61.5
61.5
66.0
77.5
77.5
80.0
63.0
63.0
66.0
72.0
72.0
75.0
44.0
39.0
35.0
44.0
39.0
35.0
1,645
1,423
1,125
1,866
7.55
6.56
5.24
90
785 × 1,012 × 1,110
785 × 1,012 × 1,110
133
 250 × 4
 250 × 4
(680 × 290) × 2
(680 × 290) × 2
3D135416
3D135416
VAM-HVE/HVLT Series
(60 Hz)
2,000
2,000
1,580
210
85
53
66.0
66.0
71.5
58.5
58.5
65.5
73.5
73.5
77.0
60.0
60.0
64.5
68.0
68.0
71.5
44.5
40.0
36.5
44.5
40.0
36.5
1,763
1,526
1,188
1,923
8.07
6.96
5.43
90