Daikin VAM Series Engineering Data page 134

Heat reclaim ventilator
Table of Contents

Advertisement

Installation Manual
VAM150-1000HVE
6-3
Wiring Examples
WARNING
Install a circuit breaker.
Failure to install a circuit breaker may result in electric shock or fire.
For Independent System
Power supply ( 1)
Circuit breaker (for
protection against
earth fault, overload,
and short circuit)
Earth
Up to 16 units of
Heat Reclaim Ventilator
can be controlled
simultaneously.
Combined operation system with air conditioner
Air conditioner
Indoor unit
Earth
P2
P1
For control by 2 remote controllers (Controlling 1 group by 2 remote controllers)
When using 2 remote controllers, one must be set to "MAIN" and the other must be set to
"secondary".
<MAIN/SUB change over method>
Refer to the installation manual of the remote controller. (Factory default setting is "MAIN".)
<Wiring method>
6-2 Wiring Connection
Connect the SUB remote controller to the device at the end of the remote
controller wiring [P2 / P1] according to
Indoor unit
P2
P1
MAIN remote
controller
For central control
F 1 F 2
F 1 F 2
IN/OUT
Heat Reclaim Ventilator
F 1 F 2
F 1 F 2
If control is performed with a central device (such as central controller), a
group number needs to be set with the remote controller.
See the manual of each central device for details.
Even when the central device is used for controls, you still use the remote
controller to change field settings. Install the remote controller in an
operable location.
For remote operations
Remote operation can be performed by connecting the external input
(Input A) to terminals J1, J2, and JC of the terminal block (X2M).
W
e r i
y t
e p
W
e r i
s
e z i
W
e r i
e l
g n
h t
Specifi cations for
external contact
10
132
Examples of wiring for each system are shown below.
Remote controller wiring and transmission
wiring are not polarized.
Power supply ( 1)
Heat Reclaim Ventilator 2
Heat Reclaim Ventilator 1
Earth
L
L
P2
P1
N
P2
P1
N
Transmission
wiring up to 500m
Remote
Remote
controller
controller
P2
P1
P2
P1
MAIN
SUB
Power supply ( 1)
Circuit breaker (for
protection against
earth fault, overload,
Heat Reclaim Ventilator
and short circuit)
Earth
L
N
P2
P1
Transmission
wiring up to 500m
Remote
Remote
controller
controller
P2
P1
P2
P1
SUB
MAIN
Method
Heat Reclaim Ventilator (1)
Heat Reclaim Ventilator (2)
2 P
P1
P2
1 P
MAIN remote
controller
Remote controller wiring [P2 / P1]
Centralized
equipment
Circuit breaker (for
Air conditioner
F 1 F 2
protection against
IN/OUT
outdoor unit
earth fault, overload,
and short circuit)
Power supply ( 1)
P2
P1
L
N
Remote controller
P2
P1
Air conditioner indoor unit
P2
P1
Remote controller
P2
P1
h S
a e
h t
d e
i v
l y n
o c
d r
o
c r
b a
e l
2 (
i w
) e r
2
. 0
5 7
. 1 -
5 2
m
m
M
a
. x
0 5
m
Contact that can open and close minimum load DC12V, 1mA
Model Name
Power supply ( 1)
1-phase 220-240/220V 50/60Hz
(1) Fresh-up operation
Supply air volume can be set at a higher level than the exhaust air (Supply
Fresh-Up) or the other way round (Exhaust Fresh-Up) by input from an external
contact point.
Set the fresh-up mode to "Supply" fresh-up or "Exhaust" fresh-up on the remote
controller.
Make settings according to
7
FIELD SETTING AND TEST RUN
Connect the external input (Input A) to terminals J2 and JC of the terminal block
(X2M).
Heat Reclaim Ventilator
Status of contact on-site
(External
J1 J2 J3 JC
contact)
Input A
(2) Forced OFF
Set the external input setting to "Forced OFF" on the remote controller.
Make settings according to
7
FIELD SETTING AND TEST RUN
Connect the external input (Input A) to terminals J2 and JC of the terminal block
(X2M).
Heat Reclaim Ventilator
(External
J1 J2 J3 JC
contact)
In case of operation combined with an external damper
The printed circuit board of the Heat Reclaim Ventilator main unit opens and closes
the no-voltage contact used for driving the damper in conjunction with the operation
of Heat Reclaim Ventilator .
Closes no-voltage contact by operation of Heat Reclaim Ventilator
Opens no-voltage contact by operation of Heat Reclaim Ventilator
Wiring instructions
The fan operation signal of Heat Reclaim Ventilator is output from terminals X1
and X2 of the terminal block (X3M) on the printed circuit board.
Do not use any code for the electric wire for linking with the
external damper. Example: VCTF (unusable); VV cable (usable)
A 1 P
X
3
M
1
X
Air conditioner
X 2
outdoor
X 3
X 4
For operation indication
Operation indication of one Heat Reclaim Ventilator will be output.
Make settings according
7
FIELD SETTING AND TEST RUN
Wiring instructions
The operation indication of Heat Reclaim Ventilator is output from terminals X3
and X4 of the terminal block (X3M) on the printed circuit board.
Power supply for indicators
1-phase 220-240/220V
A 1 P
X
3
M
X
1
X 2
X 3
X 4
Indicator
(locally procured)
Instructions on connecting transmission wiring to terminal X3M
Bundle the lead wires with the
clamp
(accessory)
X3M
A1 P
EDMMT712101
VAM150HVE
VAM250HVE
VAM350HVE
VAM500HVE
VAM650HVE
VAM800HVE
VAM1000HVE
.
Operation of the unit
Short circuit
Fresh-up operation
OPEN
Normal operation
.
Status of contact on-site
Operation of the unit
Forced OFF (remote
Short circuit
controller not permitted)
Input A
OPEN
Normal operation
Contact capacity
No-voltage contact
AC220-240V 240VA
.
Contact capacity
No-voltage contact
AC220-240V 240VA
Bundle the lead wires with the
clamp
(accessory)
English
VAM-HVE/HVLT Series