Daikin VAM Series Engineering Data page 59

Heat reclaim ventilator
Table of Contents

Advertisement

EDMMT712101
Auto cut-off control
Purpose • Functions
This is a function to prevent Heat Reclaim Ventilator Unit from operating for a long period of time due to failure to turn it off.
Unit operation
Judgement criteria for auto cut-off control
1. Judgment by indoor/outdoor temperature sensor (standard equipment)
• If the difference between the indoor and outdoor temperatures remains within the specified range for a certain period of time during
operation, the auto cut-off control is activated.
• The time taken for the above auto cut-off prevention control to be activated can be changed by making field settings.
• Select field setting options " 01", " 02" or " 03" based on the estimated daily operating hours.
2. Judgment by indoor humidity sensor (optional accessory)
Conditions: When the indoor (RA) humidity sensor
BRYH241A100 is used:
• Auto cut-off control is activated when indoor humidity of
80% and above is detected while the unit is in operation.
• Select the setting position 11 "Humidity judgment" of the
field setting.
• When an indoor humidity sensor (optional accessory) is
used, it is recommended to change the setting to "humidity
judgment".
Switch number that needs to be changed for the system
Field settings using remote controller is required.
Field settings using remote controller
Setting descriptions
Auto cut-off function
Factory default setting
VAM-HVE/HVLT Series
Setting
Mode
switch
No.
01
No.
18
Temperature judgment
12
(28)
(exceeding 12 hours)
Operation when auto cut-off control is activated (common for
temperature and humidity judgment)
• The unit stops for 50 minutes and then runs for 10 minutes.
After that, a judgment is made whether to resume operation.
• During bypass mode, the mode is automatically switched to
the heat exchange mode.
Conditions for return from auto cut-off control
• Judgment by indoor/outdoor temperature sensor
The unit will return from auto cut-off control if the difference
between indoor and outdoor temperatures remains out of the
specified range for 5 minutes while in operation.
• Judgment by indoor humidity sensor (optional accessory)
The unit will return from auto cut-off control if the room
humidity remains below 80% for 5 minutes while in operation.
• The unit resets from auto cut-off control by turning it OFF →
ON again using remote controller.
(The data in parentheses under "Setting position" is estimated daily operating hours)
Setting position
02
03
Temperature judgment
Temperature judgment
(8~12hours)
(below 8 hours)
Control System
10
11
OFF
Humidity judgment
57