Daikin VAM Series Engineering Data page 55

Heat reclaim ventilator
Table of Contents

Advertisement

EDMMT712101
BRP4A50A: Heater Control Kit
Operation range of the Heat Reclaim Ventilator (VAM series) is " –15°C to 50°CDB 80% RH or below."
When operating the Heat Reclaim Ventilator (VAM series) at or below –10°C of the outdoor air temperature, use preheater (field
supplied) to preheat outdoor air.
This kit is required for preheater to ON / OFF delay control. (Initial setting is required.)
Cautions
For electric heater, safety devices and installation location, follow the standards or regulations of each country.
Use nonflammable duct for the electric heater. Be sure to keep 2 m or more between the heater and Heat Reclaim Ventilator
(VAM series) for safety.
For the Heat Reclaim Ventilator (VAM series), use a different power supply from that of the electric heater and install a circuit
breaker for each.
Electric heater capacity formula
Heat capacity P (kW) = 0.29 Airflow rate Temp. / 860
For VAM500HVE/HVLT when Airflow rate = 500 m
–20°C to –10°C (Temp. = 10°C)
P = (0.29 500 10) / 860 = 1.68 (kW)
Check the temperature rise at low notch.
For 2kW heater, when 300 m
T = (860  P) / (0.29  Airflow rate)
= (860  2) / (0.29 300) = 19.7°C
Therefore – 20 + 19.7 = –0.3°C
Cautions at initial setting
Make sure to set remote controller of Heat Reclaim Ventilator (VAM series) at initial setting as follows :
(for ON / OFF delay)
Heater control kit setting
Heat Reclaim Ventilator
(VAM series)
Heater operating condition
Heater starts operation when it is judged as Heating operation.
(Judged from VRV signal of heating operation or Heat Reclaim Ventilator (VAM series) signal of thermostat.)
ON / OFF delay
Heater starts 10 seconds after Heat Reclaim Ventilator (VAM series) starts operation.
Fan stops 3 minutes later after Heat Reclaim Ventilator (VAM series) stops operation.
VAM-HVE/HVLT Series
3
/ h (Ultra-high) and preheater so that the outdoor temp. rise from
3
/ h
Mode No.
Setting switch no.
19 (29)
8
FAN
EH
10 sec. delay
Setting position
03 or 04
ON
OFF
heat
cool
on
OFF
on
OFF
3 min. FAN delay
Control System
53