Wiring Connection Method
(1) Remove 2 mounting screws of the electrical component box to open it.
(2) Perform installation of remote controller and power supply wiring.
Fix the power supply wiring, earth wires, and transmission wiring
(signal line and remote controller) securely in place with the clamp
(accessory) as shown in the figure on the right.
Electrical
component box
(3) When closing the electrical component box, make sure that the cover
catches no wire, and then fix it securely with 2 mounting screws.
WARNING
Form the wiring orderly so that the electrical component box can be securely attached.
Electric wires that got pinched or the electrical component box that does not sit properly may
cause electric shock or fire.
Connecting power supply wiring and earth wires>
Pass the power supply wiring and the earth wires through the wiring through-
hole (upper) into the electrical component box, as shown in the figure on the
right.
Connect the power supply wiring to the terminal block (X1M).
Connect the earth wires to the earth
terminals.
Take out the earth wire from the notch of the
cup washer and lay the wire carefully so that
the washer will not catch other wires.
Otherwise, the earth wire may not contact sufficiently, and the earthing
effect of the wire may be lost.
Route the wiring so the earth wire and the round crimp-style terminal will
not come off of the sheet metal as shown in the figure on the right.
If the power supply wiring, earth wire, and round crimp-style terminal come
off the sheet metal, they may contact the connector when the electrical box
is closed, resulting in damage.
Fix the power supply wiring and earth wires securely to the resin clamps
(2 locations) with the clamp 3 (accessory). (Enlarged view – 1)
<Connecting remote controller wiring and transmission wiring (low voltage)>
See the "Remote Controller Installation Manual" that comes with the remote
controller for details on installation of and wiring for the remote controller.
Pass the remote controller wiring and the transmission wiring through the
wiring through-hole (lower) into the electrical component box, as shown in
the figure on the right.
Connect the remote controller wiring to [P1/P2] and the transmission wiring
to [F1 / F2] of the terminal block (X1M), respectively. (No polarity: Enlarged view – 2)
Fix the power supply wiring and earth wires securely to the resin clamps
(1 locations) with the clamp ③ (accessory). (Enlarged view – 1)
<CAUTION>
Make sure that all wiring is securely connected to the respective
terminal, using the specified wires, and the sheath section is fixed with a
provided clamp, ensuring that external forces do not act on the terminal.
Use the correct screwdriver for tightening the terminal screws.
If the screwdriver's blade is too small, the head of the screw might be
damaged, and the screw will not be properly tightened.
If the terminal screws are tightened too hard, the screws might be
damaged.
Refer to the table below for the tightening torque of the terminal screws.
Earth terminal (M4)
Terminal block (X1M, X2M, X3M) (M3.5)
When installing the unit upside down, fix the external wiring (power
supply wiring, earth wires, remote control wiring, and transmission
wiring) to the push mounts (1 location each) with the clamp ③
(accessory) as shown in the figure on the right. (Enlarged view – 4)
Condensation water may enter the electrical component box and cause
a failure.
8
130
Mounting screw
Wiring through-hole
Spring washer &
plain washer
Earth
screw
Earth wire and round crimp-style terminal
Spring washer &
Cup washer
plain washer
Notch
Earth
Round crimp-style
screw
terminal
Tightening torque (N·m)
1.69±0.25
0.8±0.08
Terminal block (X1M)
Earth terminal (M4 screw + spring washer + plain washer + cup washer)
Enlarged view - 1
Resin clamp
Earth wire
Power supply
wires
Clamp ③
(accessory)
NOR.
H
M
Clamp ③ (accessory)
X1M
(for power supply wiring and earth wires)
Wiring through-hole
Clamp ③ (accessory)
Factory default setting
(for power supply wiring and earth wires)
Enlarged view - 3
Cup washer
Clamp ③
(accessory)
Do not change
Notch
Wiring
Round crimp-style
Fix the remote controller wiring and transmission wiring securely with a clamping sheet.
terminal
<CAUTION>
Resin clamp
Wind the clamping sheet only
Sheet metal
around the resin-coated section so
that the wiring will not contact the
edge of the sheet metal.
Do not allow it to come off of the sheet metal
<Prohibition>
Do not clamp low voltage wires together with high voltage wires.
Otherwise, electrical noise (external noise) could cause malfunction or failure.
In case of reverse installation
Clamp
(accessory)
(for remote controller wiring and transmission wiring)
Clamp
(accessory)
(for power supply wiring and earth wires)
Enlarged view – 4
Clamp
(accessory)
Wiring
Push mount
EDMMT712101
Electrical component box
Printed circuit board
<Prohibition>
Never connect the power supply
wiring to the terminal block.
Connect transmission wirings securely
using round crimp-style terminals.
Termi n al bl o ck (X3M)
X3M
(for combi n ed operati o n wi t h external damper/operati o n i n di c ati o n)
Terminal block (X1M)
(for remote controller / transmission wiring)
Terminal block (X2M) (for external input)
X2M
Enlarged view - 2
P2 P1 F1 F2
J1 J2 J3 JC
Remote
No-voltage
controller Central
NOR.
external input
H
Connect the remote controller and transmission wiring.
M
Do not change the switch settings. SS1 is the switch
setting for remote control.
The unit does not operate if the setting is changed.
Resin coated section
Edge of sheet metal
English
3P645058-1
VAM-HVE/HVLT Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents