Control System
Introduction to Major Connection Terminals
Terminal
L N
Power terminal
A remote controller connection terminal and connection terminal for energy-
P1 P2
saving interlocking with indoor unit of commercial multi air conditioners
(building multi)/SkyAir.
This terminal receives information when centralized control equipment is
F1 F2
connected.
(J1), (JC) terminal Fresh-up operation by external input
J
J
J
JC
1
2
3
(J2), (JC) terminal Distant control by external input
Please refer to pages 42-44 for switching to other functions.
Field Settings of "Centralized Zone Interlock Setting" Using Remote Controller
When Heat Reclaim Ventilator Unit is connected to the centralized transmission line (between (F1) and (F2) terminals),
it is necessary to consider changing the default field setting of "centralized zone interlock setting" using the remote
controller.
Combination with centralized control-related equipment
Centralized control-related equipment
Unified
Central remote
ON/OFF
controller
controller
1~4 units
1~4 units
1~16 units
1~4 units
1~4 units
1~16 units
1~16 units
1~16 units
POINT
1. When zone interlock is set to "Yes", priority
is given to energy-saving interlocked control
with commercial multi air conditioners (building
multi). Therefore, individual start/stop of Heat
Reclaim Ventilator Unit cannot be performed
with the central remote controller or Unified ON/
OFF controller.
If there are no commercial multi air conditioners
(building multi) to be interlocked within the
zone, set the zone interlock to "No". (③ and ④
on the right)
2. When zone interlock is set to "No", priority is
given to independent start/stop of Heat Reclaim
Ventilator Unit. Accordingly, energy-saving
interlocked control is not performed.
3. Generally, do not set the precooling/preheating
operation when independent ventilation
operation is started/stopped with a centralized
control equipment. If the precooling/preheating
operation is set, the unit will start operating
after the set time has elapsed.
24
Function Descriptions
Wiring adapter
schedule
for electrical
timer
appendices
1 unit
1 unit
1 unit
1 unit
1 unit
Sample system
Central remote
Unified ON/OFF
controller
controller
About ①
Basically, the operations and displays that
are performed using remote controller for air
conditioner can be carried out with the central
remote controller. However, it is not possible
to carry out independent ventilation operation,
ventilation mode switching and air volume
switching using the central remote controller.
About ②
It interlocks with indoor units within the same
zone. Independent ventilation operation mode can
be set on the central remote controller.
Independent operation cannot be performed using
the Unified ON/OFF controller.
About ⑤
When a central remote controller is used and zone
control of multiple units is not performed, one unit
becomes one zone.
To change ventilation rate, etc. other than the field
settings, connect the remote controller to Heat
Reclaim Ventilator Unit.
For other details, please see page 59.
Notes) 1. All the system configurations in this
section use commercial multi air
conditioners (building multi) as an
example. The same controls can be
performed when the air conditioners
are replaced with the SkyAir series.
2. The system configurations in this
section use wired remote controllers
as an example. The same applies
to the cases using wireless remote
controllers.
Operations / Functions
Energy saving
Start/Stop
interlocking
(from centralized
(Automatic judgement)
control)
×
×
×
×
Simultaneous operation is not available.
×
Simultaneous operation is not available.
×
×
×
(Batch ON/OFF only)
×
×
(Batch ON/OFF only)
Zone1
Remote controller
Zone 3
Zone 2
Zone interlock
Zone interlock
"No"
EDMMT712101
○: Possible ×: Impossible
Field setting
(Centralized zone
interlock setting)
×
Yes
×
No
×
Yes
No
×
Yes
×
No
×
Yes
No
No
No
×
Yes
No
×
Yes
No
Zone interlock
Zone interlock
"Yes"
"Yes"
Zone interlock
"No"
"No"
VAM-HVE/HVLT Series

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents