Daikin VAM Series Engineering Data page 171

Heat reclaim ventilator
Table of Contents

Advertisement

EDMMT712101
2. CO
sensor installation
2
(1) Loosen the screw 2, then remove the screw 1 (※1).
(※1): The screw positions may differ depending on models.
(2) Install the CO
(※2): Be careful not to get the damper wire or indoor thermistor wire caught in the sensor.
For VAM150H(S), VAM250H(S), VAM150HS, and VAM250HS,
the humidity sensor (indoor side) is installed nearby.
If the CO
2
cannot be installed in the correct position so install the CO
as shown in the figure on the right.
(2) Damper Wire (red)
(1)(2) Screw 2
(2) Indoor
Thermistor wire
3. Wiring connection of CO
(1) Remove the 2 fixing screws of the electrical box, then open the electrical box.
(2) Bring out the wire from the inside of the unit through the lower bush (weak elec. wire side),
then firmly insert it to the X14A connector (white) on the print circuit board A1P. (See Arrow View A)
(3) Bundle the CO
so that there is no stack (※1, See Arrow View B).
(4) Bundle the excess wires and secure them with the clamp inside the electrical box. (See Arrow View A)
(5) Close the electrical box and tighten the 2 fixing screws on the electrical box, be careful not to get any wire caught by the screws.
(6) After binding, cut off the excess edge of the clamp.
(3)(6) Clamp
※1
Fix near the clamp
(2 places)
4. Installing the components
Close the electrical box, then install the components with the procedure of
1. Removing the components , install the parts in the following order (2) o (1).
VAM-HVE/HVLT Series
sensor as shown in the figure and tighten the screw 1 and 2.
2
sensor is not installed properly, the humidity sensor (indoor side)
(2) Damper Wire (white)
(1)(2) Screw 1
sensor
2
sensor wire and damper wire (red) together with the indoor thermistor wire by the 2 clamps
2
(2)(3) CO
Sensor
2
(1)(5) Electrical Box
Open
Clamp
(2) Bush
(2)(3) CO
(3) Damper Wire (red)
CO
Sensor Fixing Screw
2
Humidity Sensor
(indoor side)
Fixing Screw
sensor
2
(1)(2) Screw 2
(2) CO
Sensor
2
CO
2
(2) X14A
Connector
(white)
(1)(5) Fixing Screw
(2 places)
Sensor
2
(3) No Slack
Arrow View B
Details of Optional Accessories
CO
Sensor Installation Position
2
For VAM150H(S) ・ VAM250H(S)
VAH150HS ・ VAH250HS
(2) CO
Sensor
2
(1)(2) Screw 1
Sensor Installation Details
Print Citcuit
Board A1P
(4) Clamp
Arrow View A
(3) No Slack
(3) Indoor Thermistor Wire
(3)(6) Clamp
JC: 2P550746-1D