Daikin VAM Series Engineering Data page 61

Heat reclaim ventilator
Table of Contents

Advertisement

EDMMT712101
Centralized management system
Batch/Individual operation [Central remote controller <DCS302CA61>]
Purpose • Functions
Able to perform batch or individual start/stop without zone management (while retaining 64 zone setting)
Unified ON/OFF controller, etc. can also be combined.
Ventilation rate and mode can be switched with DCS302CA61.
POINT
  G roup number for centralized control needs to be set by making field settings.
Example of control wiring
Central remote controller
Power supply
P1 P2
Indoor unit
P1 P2
Remote controller
P1 P2
Heat Reclaim
Ventilator Unit
P1 P2
Remote controller
Switch number that needs to be changed for the system
Field settings using remote controller
Centralized zone interlock setting ... "No" [Remains at the factory
default setting]
Essential optional accessory
  C entral remote controller : DCS302CA61.
VAM-HVE/HVLT Series
T1 T2
D1
D2
F1
F2
TeS1
F1 F2
P1 P2
Heat Reclaim
Ventilator Unit
P1 P2
Remote controller
F1F2
P1 P2
Heat Reclaim
Ventilator Unit
P1 P2
Remote controller
F1F2
F1F2
Centralized zone
interlock setting
Factory default setting
Control System
Setting
Setting position
Mode
switch
No.
01
No.
17 (27)
8
No
02
Yes
59